Fitting The Coaxial Flue (Ø 60/100 Horizontal) - Ariston Genius he 24 Installation And Servicing Instrucnions

Gas fires condensing wall hung combination boilers
Table of Contents

Advertisement

installation
Warning
The exhaust gas ducts must not be in contact with or close to
inflammable material and must not pass through building struc-
tures or walls made of inflammable material.
When replacing an old appliance, the flue system must be chan-
ged.
Installation with extension
Fitting the Coaxial Flue
(Ø 60 / 100 Horizontal)
Contents:
1x Silicone O-Ring (60mm)
1x Elbow (90°)
x Wall Seals (Internal & External)
1x Flue Pipe including Terminal (1 metre - 60/100)
x Flue Clamps
4x Screws
x Seals
Once the boiler has been positioned on the wall, fit the rubber
flue seal into the internal flue turret (see diagram opposite),
insert the elbow into the socket and rotate to the required po-
sition. note: It is possible to rotate the elbow 360° on its vertical
axis.
Using the flue clamp, seals and screws supplied (Fig 4) secure the
elbow to the boiler.
The 1 metre horizontal flue kit (3318073) supplied is suitable for
an exact X dimension of 753mm.
Measure the distance from the face of the external wall to the
face of the flue elbow (X - Fig ), this figure must now be su-
btracted from 753mm, you now have the total amount to be cut
from the plain end of the flue.
Draw a circle around the outer flue and cut the flue to the requi-
red length taking care not to cut the inner flue, next cut the inner
flue ensuring that the length between the inner and outer flue is
maintained. (Fig 4).
16
Supplied By www.heating spares.co Tel. 0161 620 6677
Important
Ensure that the flue is not blocked.
Ensure that the flue is supported and assembled in accordance
with these instructions.
Installation without extension
slope
* pente
slope 5 mm per metre
* pente 5 mm par mètre
e.g.
X = 555mm
753-555 = 198mm (Length to be cut from the plain end of the
flue).
Once cut to the required length, ensure that the flue is free from
burrs and reassemble the flue. If fitting the flue from inside of the
building attach the grey outer wall seal to the flue terminal and
push the flue through the hole, once the wall seal has passed
through the hole, pull the flue back until the seal is flush with the
wall. Alternatively, the flue can be installed from outside of the
building, the grey outer seal being fitted last.
Should the flue require extending, the flue connections are push
fit, however, one flue bracket should be used to secure each
metre of flue.
Note: See table for maximum and minimum flue runs.
Level
Fig. 3
Level
150 mm