Cooling System; Esd Prevention - HP MSR1003-8S Installation Manual

Hide thumbs Also See for MSR1003-8S:
Table of Contents

Advertisement

Table 4 Harmful gas limits in the equipment room
Gas
SO
2
H
S
2
NH
3
Cl
2

Cooling system

The MSR1000 router adopts left to right airflow for heat dissipation.
Figure 1 Airflow through the MSR1000 chassis
To ensure good ventilation, the following requirements must be met:
Leave at least 10 cm (3.94 in) of clearance at the air inlet and outlet vents.
The installation site has a good cooling system.

ESD prevention

CAUTION:
Check the resistance of the ESD wrist strap for safety. Make sure the resistance reading is in the range of
1 to 10 megohm (Mohm) between human body and the ground.
To prevent electrostatic discharge (ESD), follow these guidelines:
Make sure the router and the floor are reliably grounded.
Take dust-proof measures for the equipment room.
Maintain the humidity and temperature at a compliant level.
Always wear an ESD wrist strap and ESD cloth when touching a circuit board or transceiver module.
An MSR1000 router does not supply an ESD wrist wrap. Prepare an ESD wrist wrap yourself.
Place the removed interface module on an antistatic workbench, with the face upward, or put it into
an antistatic bag.
Max. (mg/m
3
)
0.2
0.006
0.05
0.01
3