EH-150/EHV Series
Using the EH-SIO Unit and
Connecting with a User-
made Cable
CPU
Link interface
EH-CPU104A
Port 2 on EH-SIO
EH-CPU208A
RS-422A/485
connector
EH-CPU316A
EH-CPU516
EH-CPU548
EHV-CPU128
EHV-CPU64
EHV-CPU32
EHV-CPU16
9-1-3
RS-485 Connections
RS-485 Connections
CPU
Link interface
EH-CPU104A
Port 1 on CPU
Module
EH-CPU208A
EH-CPU316A
EH-CPU516
EH-CPU548
EHV-CPU128
CPU Unit serial
port
EHV-CPU64
EHV-CPU32
EHV-CPU16
76
EH-S10
Uint
Hitachi PLC
Connection Diagram
RS-422/485 Connector
on CPU Module Port
(RS-422) on Hitachi PLC
Pin No.
Signal
SD+
1
SD−
2
3
RD+
RD−
4
TERM
5
SG
6
Note Settings depend on the port and communications method. Check
the communications settings given previously.
Hitachi PLC
Connection Diagram
Refer to the previous RJ45 Modular Port diagram for the pin numbers for the
RJ45 Connector.
RJ45 Connector on CPU
Module Port (RS-485) on
Hitachi PLC
Signal
Pin No.
SG
1
-
2
-
3
SD+
4
SD−
5
RD−
6
7
RD+
8
-
User-made cable
Connection diagram
To power
PT
supply
Pin No.
1
2
3
4
5
6
7
Terminator setting (built-
8
in 120 Ω resistance)
User-made cable
Connection diagram
To power
PT
supply
Pin No.
1
2
3
4
5
6
7
Terminator setting (built-
8
in 120 Ω resistance)
Section 9-1
PT
NV3W,
NV4W, or
NV3Q for RS-
422A
Signal
+
-
NV3W,
FG
NV4W, or
+SD
NV3Q for RS-
−SD
422A
+RD
−RD
PT
PT
NV3W, NV4W,
or NV3Q for
RS-485
Signal
+
-
NV3W, NV4W,
FG
or NV3Q for
+SD
RS-485
−SD
+RD
−RD
PT