Addressable external alarm indicator

Advertisement

Installation of FDCAI181:
1.
Remove the white cover cap (press the black cam).
2.
Mount the base plate (Fig. 2) on a wall or recess-mounted socket using 2 ... 4 screws with max. diameter 3 mm.
3.
Connect the alarm indicator in accordance with the connection diagram (Fig. 3, Fig. 6).
4.
Refit the white cover cap.
5.
Snap the white cover cap into place.
Installation of additional frame AI330:
For surface-mounted cable entry the additional frame AI330 must also be mounted.
Max. cable diameter: 10 mm
1.
Mount the additional frame AI330 (accessory) on a wall or recess-mounted socket using two screws with max.
diameter of 4 mm (Fig. 4, Fig. 5).
2.
Remove the white cover cap from alarm indicator FDCAI181 (press the black cam).
3.
Attach the base plate of the alarm indicator to additional frame AI330 with 2 wood or sheet-metal screws of di-
ameter 3 mm, max. 16 mm long.
4.
Connect the alarm indicator in accordance with the connection diagram (Fig. 3, Fig. 6).
5.
Refit the white cover cap.
6.
Snap the white cover cap into place.
Dimensions
85
85
Technical data
Siemens Building Technologies
CPS Fire Safety
FDCAI181
32
Operating voltage
Operating current (quiescent)
Blinking cycle
Load factor
Connection terminals
Operating temperature
Storage temperature
Humidity
Communication protocol
Color
Protection category
AI330
16
85
85
DC 12... 33 V
<200µA
1s: Locate or Alarm
0.5s: Locate when Alarm
1
2
1.0...1.5 mm
-10 ... +55 °C
-20 ... +70 °C
≤95 % rel
FD18-BUS
white, ~RAL 9010