Panasonic U-4LE1E5 Service Manual page 96

Mini vrf system
Hide thumbs Also See for U-4LE1E5:
Table of Contents

Advertisement

3. Mini VRF System Alarm Codes
E07 Error in Outdoor Unit Transmitting Signal to the Indoor Unit
1.
Error Detection Method
It is judged an error when a unit itself cannot receive (discrepancy) a signal within a 3-minute period that it had sent.
Outdoor main PC board error
The setting of the terminal resistor select switch on the outdoor main PC board is set incorrectly.
2.
Error Diagnosis
1 Outdoor
1-1
unit
control
PC board
1-2
1-3
1-4
1-5
For information on the procedures for replacing the outdoor main PC board, refer to the manual that is packaged with the
service board.
(for single-phase outdoor unit PC board)
5
Is the indoor/outdoor operation line connected to more than one
outdoor unit? (Network wired?)
Is the SHORT on the terminal resistor switch on the outdoor main
PC board set to one unit, and the others are OPEN?
Is the terminal resistor select switch on the outdoor main PC board
set to OPEN?
Is the indoor/outdoor operation line opened or shorted?
Replace the outdoor unit main PC board.
TERMINAL
(for 3-phase outdoor unit PC board)
TERMINAL
5 - 16
Mini VRF SYSTEM
Trouble Diagnosis
Yes
1-2
No
1-3
Yes
1-4
Set the SHORT to
No
one unit only
Make the SHORT
Yes
setting
No
1-4
Yes
Correct the wiring
No
1-5

Advertisement

Table of Contents
loading

This manual is also suitable for:

U-6le1e8U-4le1e8U-5le1e5U-5le1e8U-6le1e5

Table of Contents