3. Mini VRF System Alarm Codes
E05 Error in Indoor Unit Transmitting Signal to the Outdoor Unit
1.
Error Detection Method
It is judged an error when a unit itself cannot receive a signal that it has sent.
Indoor unit control PC board error
The setting of the terminal resistor select switch on the outdoor unit main PC board is set incorrectly.
2.
Error Diagnosis
1 Indoor
1-1
unit
control
PC board
1-2
1-3
1-4
1-5
For information on the procedures for replacing the indoor unit's control PC board, refer to the manual that is packaged with
the indoor unit service board.
(for single-phase outdoor unit PC board)
5
Is the indoor/outdoor operation line connected to more than one
outdoor unit? (Network wired?)
Is the SHORT on the terminal resistor select switch on the outdoor
main PC board set to one unit, and the others are OPEN?
Is the terminal resistor select switch on the outdoor main PC board
set to OPEN?
Is the indoor/outdoor operation line opened or shorted?
Replace the indoor unit control PC board.
TERMINAL
(for 3-phase outdoor unit PC board)
TERMINAL
5 - 14
Mini VRF SYSTEM
Trouble Diagnosis
Yes
1-2
No
1-3
Yes
1-4
Set the SHORT to
No
one unit only
Make the SHORT
Yes
setting
No
1-4
Yes
Correct the wiring
No
1-5