• MFC 6000 • MFC 8000 • MFC 10000 NOTE: Refer to the AERCO MFC Series Installation Manual, GF-146-IN, for preliminary assembly and installation instructions and information. Latest Update: 12/29/2015 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913...
6.3 Flow Rate adjustment ........................35 6.4 Electrode Positioning ......................... 36 6.5 Burner Setup............................37 6.6 Hydraulic Connections ........................38 6.7 Pump ..............................39 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 2 of 170 OMM-0104_94 Ph.: 800-526-0288 12/29/2015...
Page 3
6.10 Pump Adjustment ..........................43 6.11 Air Damper Adjustment ........................43 6.12 Ignition Pilot Adjustment ......................... 43 6.13 Adjustments before First Firing (Gas Operation) ................44 6.14 Startup for MFC 3000 Dual Fuel Burner ..................46 6.14.1 Gas/Air Delivery Adjustment ....................47 6.14.2 Adjusting Oil/Air Delivery ......................
Page 4
10.16.1 Combustion Air Adjustment ....................118 10.16.2 Air Adjustment for Maximum Output .................. 118 10.16.3 Gas/Air Delivery Adjustment ....................118 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 4 of 170 OMM-0104_94 Ph.: 800-526-0288 12/29/2015 GF-146...
Page 5
SECTION 13: MFC SERIES MAINTENANCE ............... 139 13.1 Preparation for Inspection and Maintenance ................139 13.2 Standard Maintenance ........................140 13.3 Burner Maintenance ........................141 13.4 RS-120 / RS-160 Burner Maintenance (MFC 3000-6000) .............. 141 13.4.1 Combustion ..........................141 13.4.2 Gas Leaks ..........................
Page 6
13.9 MFC 8000-10000 Sequence of Operation Diagram ..............147 APPENDIX B – ELECTRICAL DIAGRAMS ................150 MFC 3000 / 4000 / 5000 / 6000 Electrical Diagrams 1-8 ..............150 MFC 8000/10000 - ElectRICAL Diagrams 1-9 ..................159 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913...
FORWARD Foreword The AERCO MFC Series boilers are modulating and condensing units. The MFC Series represents a true industry advancement that meets the needs of today's energy and environmental concerns. Designed for application in any closed loop hydronic system, the MFC Series modulating capability relates energy input directly to fluctuating system loads.
In addition to all the requirements included in this AERCO Instruction Manual, the installation of units MUST conform with local building codes, or, in the absence of local codes, ANSI Z223.1 (National Fuel Gas Code Publication No. NFPA-54) for gas-fired boilers and ANSI/NFPASB for LP gas-fired boilers, as well as NFPA 31 “Standard...
3. Inspect exhaust vent and air inlet duct work (if applicable). 4. Perform initial startup per Chapter 5. 5. Perform scheduled maintenance procedures per Chapters 6 of this manual. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0104_94 Page 9 of 170 Ph.: 800-526-0288...
• Prior to unit operation, the complete gas train and all connections must be leak tested using a non-corrosive soap. • AERCO provides an optional external CO Detector, part number 58092. It can be installed and conFigured to simply sound an alarm or to shut down the boiler(s) if CO concentrations rise above a configurable threshold.
Page 11
____________________________________________________________________________ [End of Extracted Information From 248 CMR 5.08 (2)] AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0104_94 Page 11 of 170 Ph.: 800-526-0288...
The warranty shall be valid only upon compliance with the instruction given in this manual. The AERCO MFC Series boilers have been built and tested in observance of ASME requirements and UL (In Process), when ordered with a factory supplied burner.
See Table A Tridicator 123675-2 Low Water Cut Off 121700 Condensate Trap 24441 Aquastat 64115 Manual Reset Aquastat 64116 Thermowell 99235 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0104_94 Page 15 of 170 Ph.: 800-526-0288 GF-146 12/29/2015...
Page 16
MFC Series Boilers User Manual CHAPTER 3 - INSTALLATION Table A - MFC Series Accessories Refer to the MFC Boiler Field Assembly (TID-0164) for more information. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 16 of 170 OMM-0104_94 Ph.: 800-526-0288...
Page 17
NUTS for CONN. PIPE LOCK WASHERS for CONN. PIPE TUBE CLEANING BRUSH DOOR OPENING TOOL Figure 2-1: MFC Factory Installed Parts AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0104_94 Page 17 of 170 Ph.: 800-526-0288 GF-146...
MFC boilers must have access to a Natural Gas line with the following minimum pressures with the unit at FULL FIRE: • MFC 3000 = 14” W.C. • Other MFC Models = 1 psi. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 18 of 170 OMM-0104_94 Ph.: 800-526-0288 12/29/2015 GF-146...
The MFC series boiler dimensions and minimum acceptable clearances are shown in Figures 4- 1 and 4-2. The minimum clearance dimensions, required by AERCO, are listed below. However, if Local Building Codes require additional clearances, these codes shall supersede AERCO’s requirements.
3.5 Boiler Room Current regulations must always be observed. Premises in which boilers will be installed should be sufficiently ventilated and permit access for maintenance operations. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 20 of 170 OMM-0104_94 Ph.: 800-526-0288...
National Electrical Code (NEC), ANSI/NFPA 70 and/or the Canadian Electrical Code (CEC) Part I, CSA C22.1 Electrical Code. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 22 of 170 OMM-0104_94 Ph.: 800-526-0288...
The boiler door should be kept closed at all times while switching hardware and the instruction steps followed in the exact order as written. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0104_94 Page 23 of 170 Ph.: 800-526-0288...
Page 24
4. Use a wrench to loosen and remove the lower right nut and remove it (Figure 3-7). STEP 4: Figure 3-7: Removing lower Right Nut with Wrench AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 24 of 170 OMM-0104_94 Ph.: 800-526-0288...
Page 25
If necessary, adjust as described in the next section. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0104_94 Page 25 of 170 Ph.: 800-526-0288...
Retighten after preventing adjustment. installation. Figure 3-11: Example Problem for Adjusting Vertical Adjustment Nut on Hinge AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 26 of 170 OMM-0104_94 Ph.: 800-526-0288 12/29/2015 GF-146...
Page 27
Figure 3-12: Adjusting Horizontal Adjustment Nut on Hinge For any problems related to the reversal and adjustment of the door, we recommend contacting AERCO technical support team at 1-800-526-0288. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0104_94 Page 27 of 170 Ph.: 800-526-0288...
For more information concerning water quality and requirements, see the MFC Boiler Application Guide, GF-148-B. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 28 of 170 OMM-0104_94 Ph.: 800-526-0288...
Once the air has been entirely released, reset the pressure to the pre-established value and close the manual and/or automatic filling valve. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0104_94 Page 29 of 170 Ph.: 800-526-0288...
Refer to section 11.1 of OMM-0108, MFC Series Boiler Installation Manual, GF-146-IN for burner installation instructions. Note that instructions are only applicable to Riello burner models RLS120, 160, 300 and RS 120, 160, 300 acquired through AERCO. For burners not acquired through AERCO, consult the respective burner manufacturer for proper installation instructions.
CHAPTER 6 – MFC 3000 DUAL FUEL BURNER 6.1 MFC 3000 Dual Fuel Burner Features Figure 6-1: MFC 3000 Dual Fuel Parts and Features AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 32 of 170 OMM-0104_94 Ph.: 800-526-0288...
Page 33
MFC Series Boilers User Manual CHAPTER 6 – MFC 3000 DUAL FUEL BURNER Key to Figure 6-1: MFC 3000 Dual Fuel Burner Parts and Features 1. Combustion head 2. Ignition electrodes 3. Screw for combustion head adjustment 4. Sleeve 5. Fan motor 6.
4. Fit the wrench through the central hole in the flame stability disk and loosen screws (1) per Figure 6-4. 5. Remove disk (2) per Figure 6-4 and replace the nozzles using the wrench (3). AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 34 of 170 OMM-0104_94 Ph.: 800-526-0288...
With smaller pressure differences, the pressure on the nozzle return can be unstable. Figure 6-5: Nozzle Pressure and Flow Rate Chart The nozzle return pressure value is indicated by the pressure gauge (1) in Figure 6-6. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0104_94 Page 35 of 170 Ph.: 800-526-0288...
6.4 Electrode Positioning WARNING! Ensure that the electrodes are positioned as shown in Figure 6-7. Figure 6-7: Electrode Positioning AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 36 of 170 OMM-0104_94 Ph.: 800-526-0288 12/29/2015...
When fitting the burner on the two slide bars, it is advisable to gently draw out the high tension cables until they are slightly stretched. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0104_94 Page 37 of 170 Ph.: 800-526-0288...
4. Now connect the other end of the hoses to the suction and return lines. Figure 6-10: Connecting the Hydraulics AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 38 of 170 OMM-0104_94 Ph.: 800-526-0288...
Whenever the length of the suction piping exceeds 66 - 98 ft., the supply line must be filled using a separate pump. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0104_94 Page 39 of 170 Ph.: 800-526-0288...
Burner operating at maximum output. • Combustion head adjusted as indicated in diagram shown in Figure 6-15. Figure 6-13: Gas Manifold Pressure Measuring Locations AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 40 of 170 OMM-0104_94 Ph.: 800-526-0288...
Page 41
1, natural gas. This value serves as a rough guide. The effective delivery must be measured at the gas meter. Maximum Output and WC Pressure Correlation Table AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0104_94 Page 41 of 170 Ph.: 800-526-0288...
The chart shown in Figure 6-15 indicates that for this delivery, the combustion head must be adjusted using notch ( 3) shown in Figure 6-14. Figure 6-15: Maximum Burner Output AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 42 of 170 OMM-0104_94 Ph.: 800-526-0288...
Position the pilot and electrode using the dimension shown in Figure 6-16. The pilot works correctly at pressures ranging from 3-4” W.C. Pilot Flange Electrode A = 1- 21/64” Figure 6-16: Ignition Pilot Adjustment AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0104_94 Page 43 of 170 Ph.: 800-526-0288 GF-146 12/29/2015...
Figure 6-18: Maximum Gas Pressure Switch 5. Adjust the air pressure switch shown in Figure 6-19 to the start of the scale. Figure 6-19: Air Pressure Switch AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 44 of 170 OMM-0104_94 Ph.: 800-526-0288...
Page 45
Before starting up the burner it is good practice to adjust the gas train so that ignition takes place in conditions of maximum safety, i.e., with gas delivery at the minimum. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0104_94 Page 45 of 170 Ph.: 800-526-0288...
NOTE: For the start-up procedure and the parameters calibration, refer to the specific instruction manual of the LMV37 electronic cam supplied with the burner. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 46 of 170 OMM-0104_94 Ph.: 800-526-0288...
4. Adjust the combustion parameter with the air servomotor and store the maximum combustion point. 5. To complete the procedure, synchronize the combustion with the two servomotors and store the different setting points. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0104_94 Page 47 of 170 Ph.: 800-526-0288...
3. If the burner locks out again, turn the knob counter-clockwise a little bit more. Figure 6-22: Air Pressure Switch AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 48 of 170 OMM-0104_94 Ph.: 800-526-0288...
Adjust the minimum gas pressure switch shown in Figure 6-25 after having performed all the other burner adjustments with the pressure switch set at the start of the scale. Adjusting the Minimum Gas Pressure Switch AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0104_94 Page 49 of 170 Ph.: 800-526-0288...
Px pressure feeds the burner, the pressure switch should be adjusted to Px + 43.5 PSI. Figure 6-26 shows the location of this adjustment. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 50 of 170 OMM-0104_94 Ph.: 800-526-0288...
The screw 6) closes the by-pass heading towards suction and the de-energized solenoid valves 8) - 9) - 2) close the passage to the nozzle. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0104_94 Page 51 of 170 Ph.: 800-526-0288...
MAX. • If subsequently the temperature or pressure increases until the load control opens, the burner progressively decreases output down to MIN. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 52 of 170 OMM-0104_94 Ph.: 800-526-0288...
Lockout Due To Firing Failure WARNING! Ensure that all lockout and safety procedures concerning all controls and valves are strictly observed. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0104_94 Page 53 of 170 Ph.: 800-526-0288 GF-146...
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 54 of 170 OMM-0104_94 Ph.: 800-526-0288...
Page 55
MFC Series Boilers User Manual CHAPTER 7 – MFC 3000 GAS ONLY BURNER Figure 7-1: MFC 3000 Gas Only Burner Parts and Features AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0104_94 Page 55 of 170 Ph.: 800-526-0288...
Page 56
1 relay k 5 relay k 3 relay k 2 relay Gas train flange Air pressure switch test point AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 56 of 170 OMM-0104_94 Ph.: 800-526-0288 12/29/2015 GF-146...
2. Tighten the 3 screws (1) fully down. 3. In the diagram in Figure 7-2, find the notch at which to adjust both air and central gas/air. Figure 7-2: MFC 3000 Gas Only Burner Parts and Features EXAMPLE: RS 120/E LN, burner output = 3750 MBtu/hr Consult the diagram in Figure 7-3 to see that for this output the adjustments are: •...
Page 58
The diagram in Figure 7-3 indicates an optimal calibration. Figure 7-3: MFC 3000 Gas Only Burner Parts and Features 4. If the pressure of gas allows it, by closing ring nut a reduction of the formation of NOx is obtained.
Burner working at maximum output. • Ring nut (2) in Figure 7-2 adjusted as in the diagram of Figure 7-3. Figure 7-5: MFC 3000 Gas Only Gas Supply Pressure Test Points AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0104_94 Page 59 of 170 Ph.: 800-526-0288...
2. In the diagram in Figure 7-6 find the pressure value closest to the result you want; read the corresponding output on the left. Figure 7-6: MFC 3000 Gas Only Burner Minimum Load Loss Chart Maximum Output Formula Example, Natural gas: •...
Pressure in combustion chamber = 1.18 “WC 6 + 1.18 = 7.15 “WC (Pressure required at pressure test point 1 in Figure 7-5) AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0104_94 Page 61 of 170 Ph.: 800-526-0288 GF-146...
Figure 7-8: Maximum Gas Pressure Switch 5. Adjust the air pressure switch per Figure 7-9 to the start of the scale. Figure 7-9: Air Pressure Switch AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 62 of 170 OMM-0104_94 Ph.: 800-526-0288...
Page 63
Before starting up the burner it is good practice to adjust the gas train so that ignition takes place in conditions of maximum safety, i.e. with gas delivery at the minimum. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0104_94 Page 63 of 170 Ph.: 800-526-0288...
NOTE: For the start-up procedure and the parameters calibration, refer to the specific instruction manual of the LMV37 electronic cam supplied with the burner. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 64 of 170 OMM-0104_94 Ph.: 800-526-0288...
3. Adjust the combustion parameters with the air servomotor and store the maximum combustion point. 4. Complete the procedure by synchronizing the combustion with the two servomotors and storing the different setting points. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0104_94 Page 65 of 170 Ph.: 800-526-0288...
3. If the burner locks out again, turn the knob counter-clockwise in small increments until it does not. Figure 7-12: Air Pressure Switch Figure 7-13: Air Pressure Switch Connection AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 66 of 170 OMM-0104_94 Ph.: 800-526-0288...
3. If the burner locks out again, turn the dial anti-clockwise again by 0.4” W.C. Figure 7-15: Minimum Gas Pressure Switch AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0104_94 Page 67 of 170 Ph.: 800-526-0288...
Cover the UV flame sensor. Firing Failure WARNING! Ensure that all lockout and safety procedures concerning all controls and valves are strictly observed. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 68 of 170 OMM-0104_94 Ph.: 800-526-0288 12/29/2015...
CHAPTER 8 – MFC 4000/6000 DUAL FUEL BURNER 8.1 MFC 4000-6000 Dual Fuel Burner Features Figure 8-1: MFC 4000-6000 Dual Fuel Parts and Features AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 70 of 170 OMM-0104_94 Ph.: 800-526-0288...
Page 71
Pump motor contactor and t hermal relay with reset button Delivery oil solenoid valve Return oil solenoid valve DIN bar for fuse holder step-down transformer and OCI 412.10 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0104_94 Page 71 of 170 Ph.: 800-526-0288 GF-146...
4. Fit the wrench through the central hole in the flame stability disk and loosen screws (1) in Figure 8-4. 5. Remove disk (2) in Figure 8-4 and replace the nozzles using the wrench (3). AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 72 of 170 OMM-0104_94 Ph.: 800-526-0288...
1), slightly decrease the pressure in the return line until they are completely eliminated. • Type A4 return flow nozzle (45°) • Delivery pressure 290 PSI AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0104_94 Page 73 of 170 Ph.: 800-526-0288 GF-146 12/29/2015...
Page 74
If pressure fluctuations are detected on the gauge (1) in Figure 8-4 at the maximum capacity of the nozzle (maximum pressure in the return line), slightly decrease the pressure in the return line until fluctuations are completely eliminated. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 74 of 170 OMM-0104_94 Ph.: 800-526-0288...
Turn the screw (6) in Figure 8-10 until the notch shown in diagram Figure 8-9 is level with the front surface of the flange (5) in Figure 8-10. Figure 8-9: Burner Maximum Output AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0104_94 Page 75 of 170 Ph.: 800-526-0288...
8.7 Air Damper Adjustment The first time the burner is fired leave the factory setting unchanged for both low and high fire operation. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 76 of 170 OMM-0104_94 Ph.: 800-526-0288...
When fitting the burner on the two slide bars, it is advisable to gently draw out the high tension cables until they are slightly stretched. Figure 8-13: Securing the Burner to the Boiler AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 78 of 170 OMM-0104_94 Ph.: 800-526-0288...
4. Now connect the other end of the hoses to the suction and return lines. Figure 8-14: Connecting the Hydraulics AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0104_94 Page 79 of 170 Ph.: 800-526-0288...
Whenever the length of the suction piping exceeds 66 - 98 ft., the supply line must be filled using a separate pump. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 80 of 170 OMM-0104_94 Ph.: 800-526-0288...
Burner operating at maximum output. • Combustion head adjusted as indicated in diagram shown in Figure 8-9. Figure 8-17: Gas Manifold Pressure Measuring Locations AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0104_94 Page 81 of 170 Ph.: 800-526-0288...
Once the burner has fired, now proceed with calibration operations. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 82 of 170 OMM-0104_94 Ph.: 800-526-0288...
Figure 8-18: Minimum Gas Pressure Switch 4. Adjust the maximum gas pressure switch shown in Figure 8-19 to the end of the scale. Figure 8-19: Maximum Gas Pressure Switch AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0104_94 Page 83 of 170 Ph.: 800-526-0288...
Page 84
Before starting up the burner it is good practice to adjust the gas train so that ignition takes place in conditions of maximum safety, i.e., with gas delivery at the minimum. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 84 of 170 OMM-0104_94 Ph.: 800-526-0288...
NOTE: For the start-up procedure and the parameters calibration, refer to the specific instruction manual of the LMV37 electronic cam supplied with the burner. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0104_94 Page 85 of 170 Ph.: 800-526-0288...
4. Adjust the combustion parameter with the air servomotor and store the maximum combustion point. 5. To complete the procedure, synchronize the combustion with the two servomotors and store the different setting points. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 86 of 170 OMM-0104_94 Ph.: 800-526-0288...
3. If the burner locks out again, turn the knob counter-clockwise a little bit more. Figure 8-23: Air Pressure Switch AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0104_94 Page 87 of 170 Ph.: 800-526-0288...
Adjust the minimum gas pressure switch shown in Figure 8-26 after having performed all the other burner adjustments with the pressure switch set at the start of the scale. Adjusting the Minimum Gas Pressure Switch AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 88 of 170 OMM-0104_94 Ph.: 800-526-0288...
Px pressure feeds the burner, the pressure switch should be adjusted to Px + 43.5 PSI. Figure 8-27 shows the location of this adjustment. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0104_94 Page 89 of 170 Ph.: 800-526-0288...
The screw 6) closes the by-pass heading towards suction and the de-energized solenoid valves 8) - 9) - 2) close the passage to the nozzle. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 90 of 170 OMM-0104_94 Ph.: 800-526-0288...
MAX. • If subsequently the temperature or pressure increases until the load control opens, the burner progressively decreases output down to MIN. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0104_94 Page 91 of 170 Ph.: 800-526-0288...
Cover the UV flame sensor. Firing Failure WARNING! Ensure that all lockout and safety procedures concerning all controls and valves are strictly observed. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 92 of 170 OMM-0104_94 Ph.: 800-526-0288 12/29/2015...
Consult the diagram in Figure 9-2 to see that for this output the adjustments are: • Outside Air: R1 = notch 8.6. • Central Air: R2 = notch 0. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0104_94 Page 93 of 170 Ph.: 800-526-0288 GF-146...
Page 94
Extension sliding bars slightly taut. Lifting rings Figure 9-3: Burner Reassembly Figure 9-4: Burner Reassembly AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 94 of 170 OMM-0104_94 Ph.: 800-526-0288 12/29/2015 GF-146...
A maximum output of 4166 MBtu/hr corresponds to 2.95” W.C. pressure. This value serves as a rough guide; the effective delivery must be measured at the gas meter. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0104_94 Page 95 of 170 Ph.: 800-526-0288...
Figure 9-7: Maximum Gas Pressure Switch 5. Adjust the air pressure switch shown in Figure 9-8 to the start of the scale. Figure 9-8: Air Pressure Switch AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 96 of 170 OMM-0104_94 Ph.: 800-526-0288...
Page 97
Before starting up the burner it is good practice to adjust the gas train so that ignition takes place in conditions of maximum safety, i.e. with gas delivery at the minimum. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0104_94 Page 97 of 170 Ph.: 800-526-0288...
NOTE: For the start-up procedure and the parameters calibration, refer to the specific instruction manual of the LMV37 electronic cam, supplied with the burner. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 98 of 170 OMM-0104_94 Ph.: 800-526-0288...
3. Adjust the combustion parameters with the air servomotor and store the maximum combustion point. 4. Complete the procedure by synchronizing the combustion with the two servomotors and storing the different setting points. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0104_94 Page 99 of 170 Ph.: 800-526-0288...
The first start-up and curve synchronization manual is supplied with the burner. The complete manual for checking and setting all parameters will be provided on application. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 100 of 170 OMM-0104_94 Ph.: 800-526-0288...
3. If the burner locks out again, turn the knob counter-clockwise in small increments until it stops locking out. Figure 9-11: Air Pressure Switch and Connection Figure 9-12: Air Pressure Switch and Connection AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0104_94 Page 101 of 170 Ph.: 800-526-0288...
3. If the burner locks out again, turn the dial anti-clockwise again by 0.4” W.C. Figure 9-14: Minimum Gas Pressure Switch AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 102 of 170 OMM-0104_94 Ph.: 800-526-0288...
Cover the UV flame sensor. Firing Failure WARNING! Ensure that all lockout and safety procedures concerning all controls and valves are strictly observed. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0104_94 Page 103 of 170 Ph.: 800-526-0288 GF-146...
The nozzle for low fire operation is the one lying beneath the firing electrodes. • Make sure that the electrodes are positioned as shown in Figure 10-3, below. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0104_94 Page 107 of 170 Ph.: 800-526-0288...
4) in Figure 10-5 supplied with the burner. Proceed as follows: AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 108 of 170 OMM-0104_94 Ph.: 800-526-0288...
Page 109
2. Screw the spacers 4) onto spacer 1) and screw 5) respectively, Figure 10-5: Combustion Head Setting 3. Once done, refit the tie rod and nuts. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0104_94 Page 109 of 170 Ph.: 800-526-0288...
3. Install the hoses where they cannot be stepped on or come into contact with hot surfaces of the boiler. 4. Now connect the other end of the hoses to the suction and return lines. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 110 of 170 OMM-0104_94 Ph.: 800-526-0288...
Whenever the length of the suction piping exceeds 66 - 98 ft., the supply line must be filled using a separate pump. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 112 of 170 OMM-0104_94 Ph.: 800-526-0288...
The setting of the combustion head depends exclusively on the maximum delivery of the burner. In case of high altitude site, consult the AERCO factory or Riello. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913...
By setting switch (1) in Figure 10-11 to “REMOTE” you activate the remote fuel selection facility. In this position, if no remote selector is fitted, the display shows the priority fuel. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0104_94 Page 115 of 170 Ph.: 800-526-0288...
Before starting up the burner it is good practice to adjust the gas train so that ignition takes place in conditions of maximum safety, i.e., with gas delivery at the minimum. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 116 of 170 OMM-0104_94 Ph.: 800-526-0288...
NOTE: For the start-up procedure and the parameters calibration, refer to the specific instruction manual of the LMV37 electronic cam supplied with the burner. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0104_94 Page 117 of 170 Ph.: 800-526-0288...
3. Adjust the combustion parameters with the air servomotor and store the maximum combustion point. 4. Complete the procedure by synchronizing the combustion with the two servomotors and storing the different setting points. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 118 of 170 OMM-0104_94 Ph.: 800-526-0288...
The first start-up and curve synchronization manual is supplied with the burner. The complete manual for checking and setting all parameters will be provided on application. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0104_94 Page 119 of 170 Ph.: 800-526-0288...
To check this, insert a combustion analyzer into the chimney, slowly close the fan suction inlet (for example with cardboard) and check that the burner locks out, before the CO in the fumes exceeds 1%. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 120 of 170 OMM-0104_94 Ph.: 800-526-0288...
3. If the burner locks out again, turn the dial anti-clockwise again by 0.4” W.C. Figure 10-16: Minimum Gas Pressure Switch AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0104_94 Page 121 of 170 Ph.: 800-526-0288...
Burner starts again automatically if the pressure goes above 261 PSI (18 bar) after burner start Figure 10-17: Maximum Gas Pressure Switch AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 122 of 170 OMM-0104_94 Ph.: 800-526-0288...
Lockout Due To Firing Failure WARNING! Ensure that all lockout and safety procedures concerning all controls and valves are strictly observed. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 124 of 170 OMM-0104_94 Ph.: 800-526-0288 12/29/2015...
Air inlet to fan 24 Air pressure test point “-” Manifold 25 Ignition pilot attachment Thermal insulation screen for securing burner to boiler AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0104_94 Page 125 of 170 Ph.: 800-526-0288 GF-146 12/29/2015...
MFC 8000 MFC 10000 Max burner output Figure 11-3: Maximum Burner Output AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 126 of 170 OMM-0104_94 Ph.: 800-526-0288 12/29/2015...
Page 127
2. Screw the spacers (4) onto spacer (1) and screw (5) respectively. 3. Once done, refit the tie rod and nuts. Figure 11-4: Adjusting the Combustion Head AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0104_94 Page 127 of 170 Ph.: 800-526-0288...
3. Fit them to flange (1) tightening the nuts and screws. Figure 11-6: Gas Train Connection CAUTION! Once assembled, the gas train should be checked for leaks. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 128 of 170 OMM-0104_94 Ph.: 800-526-0288...
Figure 11-8: Maximum Gas Pressure Switch 5. Adjust the air pressure switch shown in Figure 11-9 to the start of the scale. Figure 11-9: Air Pressure Switch AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 130 of 170 OMM-0104_94 Ph.: 800-526-0288...
Page 131
Before starting up the burner it is good practice to adjust the gas train so that ignition takes place in conditions of maximum safety, i.e., with gas delivery at the minimum. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0104_94 Page 131 of 170 Ph.: 800-526-0288...
NOTE: For the start-up procedure and the parameters calibration, refer to the specific instruction manual of the LMV37 electronic cam supplied with the burner. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 132 of 170 OMM-0104_94 Ph.: 800-526-0288...
Adjusting Gas/Air Delivery – Continued AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0104_94 Page 133 of 170 Ph.: 800-526-0288...
The first start-up and curve synchronization manual is supplied with the burner. The complete manual for checking and setting all parameters will be provided on application. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 134 of 170 OMM-0104_94 Ph.: 800-526-0288...
On RS 300-400-500/E burners the air pressure switch is fitted in a "differential" mode, that is, with two pipes connected to the specific pressure test points “+” and “-” 22) and 23) in Figure 11-1. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0104_94 Page 135 of 170 Ph.: 800-526-0288...
3. If the burner locks out again, turn the dial anti-clockwise again by 0.4” W.C. Figure 11-15: Minimum Gas Pressure Switch AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 136 of 170 OMM-0104_94 Ph.: 800-526-0288...
Cover the UV flame sensor. Firing Failure WARNING! Ensure that all lockout and safety procedures concerning all controls and valves are strictly observed. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0104_94 Page 137 of 170 Ph.: 800-526-0288 GF-146...
Cover the UV flame sensor. Firing Failure WARNING! Ensure that all lockout and safety procedures concerning all controls and valves are strictly observed. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 138 of 170 OMM-0104_94 Ph.: 800-526-0288 12/29/2015...
CAUTION: Before performing any maintenance on the boiler, ensure that the electrical connections and grounds have been made according to current standards. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0104_94 Page 139 of 170 Ph.: 800-526-0288...
FIGURE 13-1: Burner Tube and Turbulator Maintenance • Check the integrity of the electrical system on the boiler. • Perform a combustion testing and adjust as necessary. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 140 of 170 OMM-0104_94 Ph.: 800-526-0288 12/29/2015...
Make sure that there are no gas leaks on the pipework between the gas meter and the burner. 13.4.3 Flame inspection Window Clean the flame inspection window (1) shown in Figure 13-2. FIGURE 13-2: Flame Inspection Window AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0104_94 Page 141 of 170 Ph.: 800-526-0288 GF-146...
Extract the UV scanner (2) Figure 13-4. • Clean the glass cover from any dust that may have accumulated. FIGURE 13-4: UV Scanner AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 142 of 170 OMM-0104_94 Ph.: 800-526-0288...
– To measure power, use a voltmeter with a 10 VDC scale, connected as illustrated in Figure 13- FIGURE 13-4: Detector Current Measurement Connections AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0104_94 Page 143 of 170 Ph.: 800-526-0288...
13.7 Gas Operation (MFC 8000-10000 Only) 13.7.1 Gas Leaks Make sure that there are no gas leaks on the pipework between the gas meter and the burner. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 144 of 170 OMM-0104_94 Ph.: 800-526-0288...
Combustion In case the combustion values found at the beginning of the inspection do not comply with local standard, codes, and/or guidelines, or otherwise exhibits improper combustion, contact AERCO technical support, for guidance in carrying out the necessary adjustments. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913...
MFC Series Boilers User Manual APPENDIX A – OPERATIONAL SEQUENCE DIAGRAMS APPENDIX A – Operational Sequence Diagrams 13.8 MFC 3000-6000 Sequence of Operation Diagram AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 146 of 170 OMM-0104_94 Ph.: 800-526-0288...
MFC Series Boilers User Manual APPENDIX A – OPERATIONAL SEQUENCE DIAGRAMS 13.9 MFC 8000-10000 Sequence of Operation Diagram AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0104_94 Page 147 of 170 Ph.: 800-526-0288 GF-146 12/29/2015...
Page 148
MFC Series Boilers User Manual APPENDIX A – OPERATIONAL SEQUENCE DIAGRAMS AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 148 of 170 OMM-0104_94 Ph.: 800-526-0288 12/29/2015 GF-146...
Page 149
MFC Series Boilers User Manual APPENDIX A – OPERATIONAL SEQUENCE DIAGRAMS AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0104_94 Page 149 of 170 Ph.: 800-526-0288 GF-146 12/29/2015...
APPENDIX A – OPERATIONAL SEQUENCE DIAGRAMS MFC 8000/10000 - ElectRICAL Diagrams 1-9 DIAGRAM LEGEND MFC 8000 / 10000 Electrical Diagrams 1-9 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0104_94 Page 159 of 170 Ph.: 800-526-0288 GF-146...
Page 160
MFC Series Boilers User Manual APPENDIX B – ELECTRICAL DIAGRAMS MFC 10000 - 1 of 9 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 160 of 170 OMM-0104_94 Ph.: 800-526-0288 12/29/2015 GF-146...
Page 161
MFC Series Boilers User Manual APPENDIX A – OPERATIONAL SEQUENCE DIAGRAMS MFC 10000 - 2 of 9 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0104_94 Page 161 of 170 Ph.: 800-526-0288 GF-146 12/29/2015...
Page 162
MFC Series Boilers User Manual APPENDIX A – ELECTRICAL DIAGRAMS MFC 10000 - 3 of 9 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 162 of 170 OMM-0104_94 Ph.: 800-526-0288 12/29/2015 GF-146...
Page 163
MFC Series Boilers User Manual APPENDIX A – ELECTRICAL DIAGRAMS MFC 10000 - 4 of 9 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0104_94 Page 163 of 170 Ph.: 800-526-0288 GF-146 12/29/2015...
Page 164
MFC Series Boilers User Manual APPENDIX A – ELECTRICAL DIAGRAMS MFC 10000 – 5 of 9 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 164 of 170 OMM-0104_94 Ph.: 800-526-0288 12/29/2015 GF-146...
Page 165
MFC Series Boilers User Manual APPENDIX A – ELECTRICAL DIAGRAMS MFC 10000 - 6 of 9 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0104_94 Page 165 of 170 Ph.: 800-526-0288 GF-146 12/29/2015...
Page 166
MFC Series Boilers User Manual APPENDIX A – ELECTRICAL DIAGRAMS MFC 10000 - 7 of 9 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 166 of 170 OMM-0104_94 Ph.: 800-526-0288 12/29/2015 GF-146...
Page 167
MFC Series Boilers User Manual APPENDIX A – ELECTRICAL DIAGRAMS MFC 10000 - 8 of 9 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0104_94 Page 167 of 170 Ph.: 800-526-0288 GF-146 12/29/2015...
Page 168
MFC Series Boilers User Manual APPENDIX A – ELECTRICAL DIAGRAMS MFC 10000 - 9 of 9 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 168 of 170 OMM-0104_94 Ph.: 800-526-0288 12/29/2015 GF-146...
Page 169
MFC Series Boilers User Manual APPENDIX A – ELECTRICAL DIAGRAMS NOTES: AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0104_94 Page 169 of 170 Ph.: 800-526-0288 GF-146 12/29/2015...