MASTER PROGRAMMING MODE continued
15. Current Day (Display Code CD)
Press the Extra Cycle button. Use this display to set the current
day on systems that have been configured as Day of Week
controls. This setting is identified by "CD" in the upper left
corner of the screen. Use the Up and Down buttons to select
from Day 1 through Day 7.
Figure 24
16. Flow Meter Type (Display Code FM)
Press the Extra Cycle button. Use this display to set the type
of flow meter connected to the control. This option setting is
identified by "FM" in the upper left corner of the screen. Use
the Up and Down buttons to select one of the eight available
settings.
Abbreviation
P0.7
t0.7
P1.0
t1.0
P1.5
t1.5
P2.0
Gen
t1.2
Figure 25
17. Meter Pulse Setting (Display Code K)
Press the Extra Cycle button. Use this display to specify the
meter pulse setting for a non-standard flow meter. This
option setting is identified by "K" in the upper left corner of
the screen. Use the Up and Down buttons to enter the meter
constant in pulses per unit volume.
Figure 26
K Range: 0.1 to 999.9 pulses per gallon.
Description
3/4" Paddle Wheel Meter
3/4" Turbine Meter
1" Paddle Wheel Meter
1" Turbine Meter
1.5" Paddle Wheel Meter
1.5" Turbine Meter
2" Paddle Wheel Meter
Generic or Other non-Fleck Meter
1.25" Turbine Meter
18. Relay Setting (Display Code RE)
Press the Extra Cycle button. Use this display to enable the
relay output. This option setting is identified by "RE" in the
upper left corner of the screen. Use the Up and Down buttons
to enable the relay using either time based (tb) or flow based
(Fb). Only one method can be used at a time.
For time based, set the desired Start Time (ST) and End Time
(ET). Time ranges available are determined by the Regen Cycle
Step Times. For flow based, set the desired Volume Interval
(VO) and Time On (TO).
Figure 27
Figure 28
ST Range: 0 to total number of cycles minus 1
Figure 29
ET Range: Start time to total of all cycles
Figure 30
Figure 31
VO Range: 1 to Total Gallon Capacity
Figure 32
TO Range: 1 to 7200 (minutes)
19. End of Master Programming Mode
Press the Extra Cycle button to save all settings and exit
Master Programming Mode.