3.3.7 Setting
The setting elements necessary for the automatic supervision and their setting ranges are shown in
the table below.
Element
[SVCNT]
[TCSPEN]
[CBSMEN]
[TCAEN]
[∑I
AEN]
y
[OPTAEN]
TCALM
ALM
∑I
y
YVALUE
OPTALM
The scheme switch [SVCNT] is set in the "Application" sub-menu. Other scheme switches are set
in the "Scheme sw" sub-menu.
3.4 Recording Function
The GRE110 is provided with the following recording functions:
Fault recording
Event recording
Disturbance recording
These records are displayed on the LCD of the relay front panel or on the local or remote PC.
3.4.1 Fault Recording
Fault recording is started by a tripping command of the GRE110 and the following items are
recorded for one fault:
Date and time
Trip mode
Faulted phase
Power system quantities
Up to the 4 most-recent faults are stored as fault records. If a new fault occurs when 4 faults have
been stored, the record of the oldest fault is deleted and the record of the latest fault is then stored.
Date and time occurrence
This is the time at which a tripping command has been initiated.
The time resolution is 1 ms using the relay internal clock.
Trip mode
This shows the protection scheme that output the tripping command.
Range
Step
ALM&BLK / ALM
OFF/ON/OPT-ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
1 - 10000
1
10 – 10000 E6
E6
1.0 – 2.0
0.1
100 – 5000 ms
10 ms
75
Default
Remarks
ALM&BLK
Alarming and blocking or alarming only
OFF
Trip circuit supervision
OFF
CB state monitoring
OFF
Trip count alarm
OFF
count alarm
∑I
y
OFF
Operate time alarm
10000
Trip count alarm threshold setting
10000
alarm threshold setting
∑I
y
2.0
y value setting
1000 ms
Operate time alarm threshold setting
6 F 2 T 0 1 7 2