4.2.6.11 Control
The GRE110 can control the Circuit Breaker(CB) open / close by the front panel keys.
The interlock function can be blocked the Circuit Breaker(CB) close command by the interlock
signals from binary input signal or communication command.
To set the control function and interlock function, do the following:
• Select "Control" on the "Set. (change)" screen to display the "Control" screen.
/
2
C o
> C o
D i
I
D i
• Enter 0(=Disable) or 1(=Enable) to select the control function use or not use and press the
ENTER key.
• Enter 0(=Disable) or 1(=Enable) to select the interlock function use or not use and press the
ENTER key.
Note: When the Control function is disabled, both the "Local" LED and the "Remote" LED are not
lit, and the sub-menu "Control" on the LCD is not displayed.
4.2.6.12 Frequency
The GRE110 can change setting of system frequency 50Hz or 60Hz.
• Select "Frequency" on the "Set. (change)" screen to display the "Frequency" screen.
/
2
F r
> F r
5
• Enter 0(=50Hz) or 1(=60Hz) to select the system frequency setting 50Hz or 60Hz and press the
ENTER key.
CAUTION
When having changed the system frequency settings, the GRE110 must reboot to enable the
setting change.