Modbus: Interoperability
1. Physical and Data Link Layer
- RS485(EIA/TIA-485) 2-wire interface
- RTU mode only
- Coding System:
8–bit binary (1 start bit, 8 data bits, 1 parity bit, 1 stop bit)
Even parity
- Address setting range: 1-247
- Baud rate setting range: 9600 or 19200
2. Application Layer
(1) Modbus response format
FC Description
01
Read Coils
02
Read Discrete Inputs
03
Read Holding Registers
04
Read Input Register
05
Write Single Coil
06
Write Single Register
07
Read Exception status
08
Diagnostic
16
Write Multiple Registers
17
Report Slave ID
43
Read device Identification (SC:14)
For FC (Function Code) = 01, 02, 03, 04, 05, 06 and 16, the response format is the same as described
in "Modbus Application Protocol Specification V1.1b".
For other FCs, the response format is as following:
07 Read Exception status
Response Data
Output Data (1byte)
bit Description
0 IN SERVICE (LED)
1 TRIP (LED)
2 ALARM (LED)
3 RELAY FAIL (LED)
4 CB CLOSED (LED)
5 CB OPEN (LED)
6 Relay fail output (BO)
7 <Reserved>
Supplementary explanation
Returns remote control enable flag
Returns BIs or LED lamp status, etc.
-
Returns value of analog inputs
Remote command and Time synchronization
Need to specify record number
Returns relay and CB status
-
Current time setting, etc.
Returns device ID
Returns device information
261
6 F 2 T 0 1 7 2
Need help?
Do you have a question about the GRE110 and is the answer not in the manual?