Toshiba GRE110 Instruction Manual page 111

Overcurrent protection relay
Table of Contents

Advertisement

I
E C 2 G I
5
N o /
Y e s
I
E C 2 G I
6
N o /
Y e s
I
E C 2 G I
7
N o /
Y e s
I
E C 2 G I
8
N o /
Y e s
I
E C N F I
1
.
2 /
2 .
4
<RS485BR>
This line is to select the baud rate when the Modbus or IEC60870-5-103 protocols are applied.
<IECBLK>
Enter 1(=Blocked) to block the monitor direction in the IEC60870-5-103 communication.
<IECNFI >
This line is to select the normalized factor (1.2 or 2.4) of the current measurand.
<IECGI1 - 8 >
These lines are to use the GI (General Interrogation) or not for user customized signals. If GI is to
be used , enter 1(=Yes).
<RS485P>
This line is to select the communication protocol when the MODBUS or IEC60850-5-103 system
applied.
<EtherP>
This line is to select the communication protocol when the IEC61850 system applied.
<61850BLK>
Select 1 (=Blocked) to block transmission from relay to BCU for IEC61850 communication. When
using the IEC61850 communication, select 0 (=Normal).
<TSTMOD>
Select 1 (=On) to set the test mode in IEC61850 communication.
<GSECHK>
This function is to alarm if any one of the GOOSE messages written in a GOOSE subscribe file
cannot be received.
Select 1 (=On) to execute a GOOSE receive check for IEC61850 communication.
<PINGCHK>
This function is to check the health of the network by regularly sending a 'Ping' to IP address which
is set on PG∗-∗.
Select 1 (=On) to execute a 'Ping' response check.
• Select the number and press the ENTER key.
0
0
This setting is displayed if submodel of
communication type is 2 and "RS485P" in
comms switch settimg is "IEC103".
0
0
This setting is displayed if "RS485P" in
0
comms switch settimg is "IEC103".
 110 
6 F 2 T 0 1 7 2