Table 6.1.1. Connector pin-out
Pin name
Description
A IN 1 -
Analog input 1. Input voltage range is from 0 to 10Vdc in voltage mode or input
A IN 1 +
current range is 4-20mA in current mode.
A IN 1 -
Analog input 2. Input voltage range is from 0 to 10Vdc in voltage mode or input
current range is 4-20mA in current mode.
A IN 1 +
D IN 1
Digital input 1. This input is optically isolated by two different voltage levels:
0...3Vdc – false; 3...26Vdc – true.
D IN 2
Digital input 2. This input is optically isolated by two different voltage levels:
0...3Vdc – false; 3...26Vdc – true.
D IN 3
Digital input 3. This input is optically isolated by two different voltage levels:
0...3Vdc – false; 3...26Vdc – true.
D IN 4
Digital input 4. This input is optically isolated by two different voltage levels:
0...3Vdc – false; 3...26Vdc – true.
Digital input ground. It is separated from module ground (power supply,
D IN -
analog input) because digital inputs are optically isolated.
Device supply. Voltage is 11- 29V ±10%
11-29V +
regulator is used inside, the smaller the voltage, the bigger the current and
vice versa (power consumption remains about the same)
11-29V -
Figure 6.1.1