CHS Series

2.4.1.3 CH Config - Warm Weather Shutdown

(CH
Config)
Warm
(WWSD) – sub-menu screen, allows the installer to
enable the WWSD function for local (i.e. non Lead
Lag) Central Heat demands, and define at what
outdoor temperature it is initiated. Use the up and
down (▲▼) buttons to navigate the menu options;
when the desired option is highlighted select by
pressing the "OK" button.
When "Warm weather shutdown" is set to one of the
"Shutdown" options, and the outdoor temperature is
above the "Warm weather shdn setpoint", CH
operation is inhibited.
CH operation is restored when the outdoor
temperature drops below the WWSD setpoint by a
fixed value of 4ºF.
Table 2-8 Warm Weather Shutdown Configuration Parameters
Parameter
Description
Enable or Disable Warm Weather Shutdown and select shutdown options
Shutdown after demand ends
Warm weather
shutdown
Shutdown immediately
Disable
Warm weather
Temperature at which local Central Heat operation is inhibited. Not applicable
when "Warm weather shutdown" is set to "Disable". Range 50°F to120°F
shdn setpoint
Figure 2-12 WWSD Configuration Screen
Weather
Shutdown
Controller and Display
Warm Weather Shutdown
Warm weather shutdown
Warm weather shdn setpoint
Slant Fin Corp.
Disable
o
60
F
Factory Settings
Disable
60°F