GAS-FIRED CAST IRON BOILERS FOR NATURAL AND L.P. PROPANE GASES
GALAXY

INSTALLATION AND OPERATING INSTRUCTIONS

CONTENTS .........................................................................PAGE
Dimensions............................ ......................................................2
Boiler Location........................................ ................................3
Boiler Foundation....................................................................3
Chimney Requirements............................. .............................3
Minimum Clearance.....................................................................3
Vent Piping..............................................................................4
Gas Piping............................................. ......................................4
Electrical Controls and Wiring.................... ............................5
Boiler Room Air Supply and Ventilation..................................5
Draft Hood Installation.............................. ..............................5
Piping at Boiler-Water Boilers................... ...........................6
Steam Controls Assembly and Installation .............................6
Piping a Steam Boiler .........................................................6,7
Vent Damper.......................................... ..............................8,9
Filling and Venting Water Systems.............. ...........................9
Burner Adjustment, Checking Gas Input...... ........................12
Controls, Safety Check .........................................................13
Low Water Cut-off Check-Out....................................................13
Pressure Control Check-Out .....................................................13
Blowing Off a Steam Boiler........................................................14
Care and Maintenance.................................. ............................15
Safety Check for Control System..........................................16
Protection From Freezing.......................... ...........................16
Water Treatment....................................................................16
Sequence of Operations............................................................17
Wiring Diagrams.......................................... .........................18-25
Pump or Valve Zoning-Water Boilers.............. ........................26
Troubleshooting Guide...............................................................27
Piping a Heating and Cooling System.......................................28
Replacement Parts...................................... ..............................28
Appendix A ................................................................................29
Heating Contractor
Address
Phone Number
Printed in U.S.A. 706
Part No. 41-0549
HOT WATER-Models GG-75H through GG-399H
LOW PRESSURE STEAM AND HOT WATER-
Models GXH-105 through GXH-300H and Models GX-225 and GX-250
LOW PRESSURE STEAM-Models GXHA-100 through GXHA-200
IMPORTANT
READ ALL OF THE FOLLOWING WARNINGS AND
STATEMENTS BEFORE READING THE
INSTALLATION INSTRUCTIONS
WARNING
LIQUEFIED PETROLEUM (L.P.)
PROPANE GAS-FIRED BOILERS
Installation location ONLY as permitted in paragraph entitled
"LIQUEFIED PETROLEUM (L.P.) PROPANE GAS-FIRED
BOILER LOCATION" on page 3 of this instruction book.
The above warning does not apply to NATURAL gas-fired boilers.
The installation must conform to the requirements of the authori-
ty having jurisdiction or, in the absence of such requirements, to
the National Fuel Gas Code, ANSI Z223.1-latest edition. The
installation must also conform to the additional requirements in
this Slant/Fin Instruction Book.
In addition, where required by the authority having jurisdiction,
the installation must conform to American Society of Mechanical
Engineers Safety Code for Controls and Safety Devices for
Automatically Fired Boilers, No. CSD-1.
This manual must be left with owner and should be hung on or
adjacent to the boiler for reference.
WARNING
This boiler, gas piping and accessories must be installed, con-
nected, serviced and repaired by a trained, experienced service
technician, familiar with all precautions required for gas-fired
equipment and licensed or otherwise qualified, in compliance
with the authority having jurisdiction.
Boiler Model Number
Boiler Serial Number
Installation Date
PUBLICATION GG-40
Rev. I

Advertisement

Table of Contents
loading

Summary of Contents for Slant/Fin GG-100H

  • Page 1: Table Of Contents

    Filling and Venting Water Systems.........9 installation must also conform to the additional requirements in Initial Start, Safety and Lighting Instructions....10-11 this Slant/Fin Instruction Book. Burner Adjustment, Checking Gas Input......12 Controls, Safety Check ............13 In addition, where required by the authority having jurisdiction, Low Water Cut-off Check-Out............13...
  • Page 2: Dimensions

    RIGHT SIDE RIGHT SIDE All GG and GX(H) GG / GX(H)-PT GX(H)-PZT-PPZT GX(H)-PZ GG SERIES HOT WATER BOILERS - DIMENSIONS IN INCHES GG-75H GG-100H GG-125H GG-150H GG-175H GG-200H GG-225H GG-250H GG-275H GG-300 GG-325 GG-350 GG-350H GG-375H GG-399H ⁄ ⁄ ⁄...
  • Page 3: Installation Requirements

    This installation must also conform to the additional require- with Part 7, Part 10 and Appendix G of the National Fuel ments in this Slant/Fin instruction book. Installation and service Gas Code ANSI Z223.1, NFPA 54, -latest edition which will to be performed by a qualified installer, service agency or the be referred to as the National Fuel Gas Code.
  • Page 4: Vent Piping

    GALAXY GAS PIPING— GALAXY GX GXH SERIES GXHA SERIES A. Local installation codes apply. The pipe joint compound used on threads must be resistant to the action of liquefied petro- MODELS GXH-105 MODELS GXH-210 TO MODELS GXHA-100, leum gases. THROUGH GXH-190 GXH-300H, GX-225 TO GXHA-120, GXHA-160 MINIMUM CLEARANCE...
  • Page 5: Electrical Controls And Wiring

    GALAXY The National Fuel Gas Code, ANSI Z223.1-latest edition speci- ELECTRICAL CONTROLS AND WIRING— A. The electrical power to the boiler must be on a separately fies openings for air under various conditions. Local codes may fused and live circuit. specify minimum opening sizes and locations.
  • Page 6: Piping At Boiler-Water Boilers

    If system pressure needs further control, add an additional NOTES: tank or install a larger capacity tank. 1. Slant/Fin makes no recommendation, nor does Slant/Fin Locate the tank near the boiler, as illustrated. imply that One Pipe Parallel and Counterflow Gravity...
  • Page 7 A Hartford Loop is recommended for low pressure steam systems with gravity condensate returns. Pipe sizes shown above for Hartford Loop are recommended by Slant/Fin. However, certain local codes may require larger pipe sizes. Consult with local authorities. ∆ The equalizer should be full size from the steam supply to the operating water level.
  • Page 8: Vent Damper

    Slant/Fin Corp. gas boiler models. These boilers must also be equipped with a plate which states that the boiler must or may be used with a Slant/Fin Corp. automatic vent damper device and indicates the proper vent damper model number. This device cannot be used with millivolt ignition system or boilers with input of 300,000 Btu/hr.
  • Page 9: Operating Instructions

    GALAXY FIGURE 8a & 8b 5. All Slant/Fin Corp. Galaxy steam boilers equipped with intermittent pilot ignition and continuous (standing) pilot systems are factory wired except for the wires to the low water cut-off and pressure cut-off. Wire these controls with wire provided with boiler (see boiler wiring diagram on boil- er).
  • Page 10: Initial Start, Safety And Lighting Instructions

    GALAXY II. CLEANING AND FILLING A NEW STEAM BOILER INSTRUCTIONS Before using steam boiler: Follow the lighting instructions that apply to the particular igni- A.Check boiler to be certain it is ready for firing. DO NOT tion system equipped on this boiler. (Also, see figures on page FIRE into an empty boiler.
  • Page 11: Warning

    GALAXY 7. Remove the pilot access panel located below and behind for gas. Be sure to smell next to the floor because some the gas control unit. gas is heavier than air and will settle on the floor. 8. Find pilot—follow metal tube WHAT TO DO IF YOU SMELL GAS from gas control.
  • Page 12: Burner Adjustment, Checking Gas Input

    Btuh Input = cu. ft. metered in 3 minutes x 1050 Btu/cu.ft. x 20 4. The higher* heating value of gas varies substantially for different localities. Consult with Slant/Fin’s Technical Service Dept. for re-orificing procedures if any of the fol- lowing apply: C.Main Burner Ignition Check-out and Pilot Adjustment...
  • Page 13: Viii. Controls, Safety Check

    GALAXY d. Check safety shutdown of gas valve by following proce- Steam controls assembly dure outlined "CARE AND MAINTENANCE" section. VIII. CONTROLS, SAFETY CHECK Check all safety controls not previously mentioned. Also, follow directions in "CARE AND MAINTENANCE" section, paragraphs IV through VII. These boilers are equipped with both a draft hood blocked vent safety switch and a rollout safety switch.
  • Page 14: Blowing Off A Steam Boiler

    GALAXY only.) Fire boiler to produce steam. If the system is heavily Replacement of Steam Boilers laden with oil, it may be difficult to obtain much more than Anytime an older steam boiler is removed from the heating sys- a pound or so of pressure. Set the pressure control at tem and replaced with a new boiler, there are certain conditions about 7 psi.
  • Page 15: Care And Maintenance

    GALAXY C.Open the SKIMMER drain valve with caution. DO NOT II. WATER LEVEL CHECK DURING HEATING SEASON: open the boiler drain valve. Fill the boiler slowly until A.Check water level regularly and add water slowly to sys- water begins to seep into the bucket from the skimmer tem when needed.
  • Page 16: Iv. Safety Check For Control System

    GALAXY Boiler Cleaning kept above freezing temperature by some means, the plumbing system is not protected. Two types of anti-freeze may be used: ETHYLENE GLY- COL, used in automobiles, has desirable properties, but is toxic. Its use may be prohibited when system water/glycol solution is in contact with a potable water vessel (as with a tankless heater).
  • Page 17: Sequence Of Operations

    GALAXY SEQUENCE OF OPERATION FOR GALAXY BOILERS EQUIPPED WITH CONTINUOUS BURNING PILOT FOR DIAGRAMS SHOWN ON PAGE 18-21. LIGHTED PILOT HEATS THERMOCOUPLE AND KEEPS PILOTSTAT OPEN. THERMOSTAT CALLS LOW LIMIT (FOR TANKLESS COIL) FOR HEAT CALLS FOR HOT WATER HOT WATER BOILERS EQUIPPED HIGH-LIMIT CONTACTS CLOSED? WITH COMBINATION AQUASTATS: NO FURTHER...
  • Page 18: Wiring Diagrams

    GALAXY WIRING DIAGRAMS FOR HOT WATER BOILERS WITH INPUT UNDER 300,000 BTU/HR MODELS WITH CONTINUOUS PILOT AND VENT DAMPER CAUTION: Label all wires prior to disconnection when servicing control. Wiring errors can cause improper and dangerous operation. “Verify proper operation after servicing.”...
  • Page 19 GALAXY WIRING DIAGRAMS FOR HOT WATER BOILERS WITH INPUT OF 300,000 BTU/HR MODELS WITH CONTINUOUS PILOT AND OPTIONAL VENT DAMPER CAUTION: Label all wires prior to disconnection when servicing control. Wiring errors can cause improper and dangerous operation. “Verify proper operation after servicing.”...
  • Page 20: Warning

    BLOCKED VENT SAFETY SWITCH MUST BE MOUNTED TO DRAFT HOOD BEFORE OPERATING THE BOILER (SEE INSTRUCTION MANUAL GG-40) BEFORE INSTALLING VENT DAMPER , READ WARNING LABEL ON THIS BOILER AND VENT DAMPER. READ SLANT/FIN VENT DAMPER INSTALLATION INSTRUCTIONS. SLANT/FIN VENT...
  • Page 21: Warning

    BLOCKED VENT SAFETY SWITCH MUST BE MOUNTED TO DRAFT HOOD BEFORE OPERATING THE BOILER (SEE INSTRUCTION MANUAL GG-40) BEFORE INSTALLING VENT DAMPER , READ WARNING LABEL ON THIS BOILER AND VENT DAMPER. READ SLANT/FIN VENT DAMPER INSTALLATION INSTRUCTIONS. OPTIONAL VENT DAMPER...
  • Page 22: Warning

    BLOCKED VENT SAFETY SWITCH MUST BE MOUNTED TO DRAFT HOOD BEFORE OPERATING THE BOILER (SEE INSTRUCTION MANUAL GALAXY GG-40) BEFORE INSTALLING VENT DAMPER , READ WARNING LABEL ON THIS BOILER AND VENT DAMPER. READ SLANT/FIN VENT DAMPER INSTALLATION INSTRUCTIONS. FOR PROPANE USE S8600M OR S8670E, FOR NATURAL GAS S8600F, S8600M OR S8670E.
  • Page 23 OPERATING THE BOILER (SEE INSTRUCTION MANUAL GG-40). BEFORE INSTALLING VENT DAMPER , READ WARNING LABEL ON THIS BEFORE INSTALLING VENT DAMPER , READ WARNING LABEL ON THIS BOILER AND VENT DAMPER. READ SLANT/FIN VENT DAMPER BOILER AND VENT DAMPER. READ SLANT/FIN VENT DAMPER INSTALLATION INSTRUCTIONS.
  • Page 24 BLOCKED VENT SAFETY SWITCH MUST BE MOUNTED TO DRAFT HOOD BEFORE OPERATING THE BOILER (SEE INSTRUCTION MANUAL GG-40). BEFORE INSTALLING OPTIONAL VENT DAMPER , READ WARNING LABEL ON THIS BOILER AND VENT DAMPER. READ SLANT/FIN VENT DAMPER INSTALLATION INSTRUCTIONS. FOR PROPANE USE S8600M OR S8670E ONLY, FOR NATURAL GAS S8600F, S8600M OR S8670E.
  • Page 25: Warning

    BEFORE INSTALLING VENT DAMPER , READ WARNING LABEL ON THIS BEFORE INSTALLING OPTIONAL VENT DAMPER , READ WARNING BOILER AND VENT DAMPER. READ SLANT/FIN VENT DAMPER LABEL ON THIS BOILER AND VENT DAMPER. READ SLANT/FIN VENT INSTALLATION INSTRUCTIONS. DAMPER INSTALLATION INSTRUCTIONS.
  • Page 26: Pump Or Valve Zoning-Water Boilers

    GALAXY PUMP OR VALVE ZONING OF WATER BOILERS COMBINATION CONTROLS WITH T Z TERMINALS*...
  • Page 27: Troubleshooting Guide

    GENERAL TROUBLESHOOTING GUIDE FOR SERVICEPEOPLE GALAXY BURNERS FAIL TO OPERATE CAUSE REMEDY 1. Safety pilot out, or flame too low. 1. Check, clean, re-light. See instructions. 2. Gas supply valve shut off. 2. Open gas valve(s). 3. Electric switch open. 3.
  • Page 28: Piping A Heating And Cooling System

    Only simple, easily identified controls and parts may be obtained locally. All other controls and parts should be identified by and ordered from Slant/Fin. Relief/Safety valves must be ASME rated for the pressure and gross output of the boiler.
  • Page 29: Appendix A

    GALAXY APPENDIX A Removal of Existing Boiler from Common Vent System "At the time of removal of an existing boiler, the following steps shall be followed with each appliance remaining connected to the com- mon venting system placed in operation, while the other appliances remaining connected to the common venting system are not in operation."...
  • Page 30 ©Slant/Fin Corp. 2006 SLANT/FIN CORPORATION, Greenvale, N.Y. 11548 • Phone: (516) 484-2600 Canada: Slant/Fin Mississauga, Ontario FAX: (516) 484-5921 • LTD/LTEE, www.slantfin.com...

Table of Contents