WIRE SIZES

The following chart contains information on wire sizes, the DC resistance of the wires and the corresponding diameters and areas of
these wires. This information can be used to calculate the voltage drop of the wires or to find an equivalent wire size.
SIZE
(AWG)
14
12
10
8
6
4
2
1
1/0
2/0
3/0
4/0
Installation & Programming Manual
Page 56
DC
CROSS-SECTIONAL AREA
Resistance
in Ohms
SQUARE
(1000 feet)
INCHES
3.14
.0032
1.98
.0051
1.24
.0082
0.78
.0130
0.50
.0206
0.31
.0328
0.19
.0521
0.15
.0657
0.12
.0829
0.10
.1045
0.08
.1318
0.06
.1662
FX & VFX "E" Series Inverter/Charger System
SQUARE
INCHES
MILLIMETERS
2.08
3.31
5.26
8.37
13.30
21.15
33.62
42.41
53.50
67.43
85.01
107.20
900-0027-2
Rev 7.1
06/08/06
APPROXIMATE
DIAMETER
MILLIMETERS
.078
1.98
.101
2.57
.126
3.20
.162
4.11
.215
5.46
.269
6.83
.337
8.56
.376
9.55
.423
10.74
.508
12.90
.576
14.63
.645
16.38