Grid Menu - Outback Power Systems Inverter/Charger FX2012ET Installation And Programming Manual

“export” fx and vfx inverter/charger
Hide thumbs Also See for Inverter/Charger FX2012ET:
Table of Contents

Advertisement

GRID MENU

The GRID category of the advanced menu section allows for adjustment of the AC input voltage window and time delays to match the
characteristics of the AC source if that AC source is the utility grid. This setting can be found in the SETUP/FX/INPUT menu. All
OutBack Power System FX's other than the "Grid-Tie" FX's have a default of GEN (generator) as the AC source. If the AC source is
the utility grid, return to the SETUP/FX/INPUT section (page 45) and change the 'AC Transfer Control' screen to GRID.
ADV-----------------
choose product:
FX
MATE
ADV/FX/PAGE1--------
choose category:
ADV
INV
CHGR
PG2
ADV/FX/PAGE2--------
choose category:
PG1
GRID
GEN
PG3
ADV/FX/GRID------P00
ac input
00.5 min
connect delay
DOWN
INC
DEC
PORT
ADV/FX/GRID------P00
ac1/grid
208 vac
lower limit
DOWN
INC
DEC
PORT
ADV/FX/GRID------P00
ac1/grid
270 vac
upper limit
DOWN
INC
DEC
PORT
ADV/FX/GRID------P00
ac1/grid
24.0 aac
input limit
DOWN
INC
DEC
PORT
ADV/FX/GRID------P00
ac1/grid
6 cycles
transfer delay
DOWN
INC
DEC
PORT
ADV/FX/GRID---------
GRID programming
completed
TOP
ADV
MAIN
Copyright 2003
OutBack Power Systems, Inc.
nd
19009 62
Ave NE, Arlington WA 98223 USA
Tel 360 435 6030
Fax 360 435 6019
Once the password has been correctly entered, the ADV - CHOOSE PRODUCT is displayed.
Selecting <FX> allows adjustment of the FX's advanced programming.
Selecting <PG2> advances the user to the second page of the advanced menu.
Selecting <GRID> allows adjustment of the AC input set points and operation.
The AC INPUT CONNECT DELAY set point adjusts the time period of when the FX sees an
acceptable AC source to when it connects the AC loads to that source. This is useful to allow the
utility grid to become stable after a utility power outage. This setting has a range between 0.2
minutes to 15 minutes in 0.1 minute increments.
The AC1/GRID LOWER LIMIT set point allows adjustment of the minimum voltage that the AC
source is allowed to be in order for the FX to connect to that source. The FX will back off the
charger if the AC source is at this lower limit. If the AC source falls below this limit, the FX will
disconnect from the AC source until it is above this value. This setting has a range between 80
vac and 220 vac in 2 vac increments.
The AC1/GRID UPPER LIMIT set point allows adjustment of the maximum voltage that the AC
source is allowed to be in order for the FX to connect to that source. If the AC source exceeds
this value, the FX will disconnect from the AC source until it is below this value. This setting has a
range between 250 vac and 300 vac in 2 vac increments.
The AC1/GRID INPUT LIMIT sets the maximum amount of current the FX allows to be drawn
from the AC source. When the AC input current limit is reached, the power draw of the battery
charger is backed off to prevent overloading the AC source. If the AC loads exceed this limit, the
FX will give a warning and start blinking the red "ERROR" LED. This setting has a range between
2.5 aac and 30.0 aac in 0.5 aac increments.
The AC1/GRID TRANSFER DELAY is the amount of time that the AC input will remain connected
to the AC source when the AC input voltage drops below the AC1/GRID lower limit setting.
Once the AC voltage has risen above the AC1/GRID lower limit setting for the AC INPUT
CONNECT DELAY time period the AC source will be reconnected. This setting has a range
between 0 cycles and 240 cycles in 1 cycle increments.
Selecting TOP returns the user to the top of the ADV/FX/GRID menu section. Selecting ADV
returns you to the advanced screen to allow selection of another product connected to the MATE.
Selecting MAIN returns the display to the MAIN screen.
FX & VFX "E" Series Inverter/Charger System
900-0027-2
Rev 7.1
06/08/06
MATE SCREENS
Installation & Programming Manual
Page 49

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents