DC
• Use crimped and sealed copper ring terminal lugs with 0.79 cm (5/16") hole or compression-type
lug to connect battery cables to DC terminals. Soldered cable lugs are also acceptable.
• Use recommended cable sizes (see page 42) to reduce losses and ensure high performance of FX
(smaller cables can reduce performance and possibly damage the unit).
• Keep cables together (e.g., using a tie-wrap) as much as possible.
• Ensure cables pass through the same knockout and conduit fittings. This helps to cancel the effects
of self-induction in the cables.
TORQUE REQUIREMENTS
CONNECTION
AC and PV breakers
DC shunt
DC battery connections
FX's DC terminals
FX's AC terminals
12
TORQUE
to 2.48 Nm/22 inch-lbs
to 20.4 Nm/15 foot-lbs
to 13.6 Nm/10 foot-lbs
to 3.38 Nm/5 foot-lbs
to 3.38 Nm/30 inch-lbs
Table 1 Torque Values for Installation