Check Codes Displayed On Remote Controller And Smms Outdoor Unit (7-Segment Display On I/F Board) And Locations To Be Checked - Toshiba MMD-AP0186HP-E Service Manual

Hide thumbs Also See for MMD-AP0186HP-E:
Table of Contents

Advertisement

9-4. Check codes displayed on remote controller and SMMS outdoor unit (7-segment
display on I/F board) and locations to be checked
For other types of outdoor units, refer to their own service manuals.
Check code
Outdoor 7-segment display
Main
remote
Check
controller
Sub-code
code
E01
E02
E03
E04
No. of indoor
units from
which signal is
received
normally
E06
E06
E07
Location
Description
System status
of
detection
Remote
Indoor-remote
Stop of
controller
controller
corresponding
communication
unit
error
(detected at
remote
controller end)
Remote
Remote
Stop of
controller
controller
corresponding
transmission
unit
error
Indoor
Indoor-remote
Stop of
unit
controller
corresponding
communication
unit
error
(detected at
indoor end)
Indoor
Indoor-outdoor
Stop of
unit
communication
corresponding
circuit error
unit
(detected at
indoor end)
I/F
Dropping out of
All stop
indoor unit
I/F
Indoor-outdoor
All stop
communication
circuit error
(detected at
outdoor end)
66
Error detection
Check items (locations)
condition(s)
Communication between
Check remote controller
inter-unit tie cable (A / B).
indoor P.C. board and remote
Check for broken wire or
controller is disrupted.
connector bad contact.
Check indoor power
supply.
Check for defect in indoor
P.C. board.
Check remote controller
address settings
(when two remote
controllers are in use).
Check remote controller
P.C. board.
Signal cannot be transmitted
Check internal
from remote controller to
transmission circuit of
indoor unit.
remote controller.
--- Replace remote
controller as necessary.
There is no communication
Check remote controller
from remote controller
and network adaptor
(including wireless) or
wiring.
network adaptor.
Indoor unit is not receiving
Check order in which
power was turned on for
signal from outdoor unit.
indoor and outdoor units.
Check indoor address
setting.
Check indoor-outdoor tie
cable.
Check outdoor termination
resistance setting (SW30,
Bit 2).
Indoor unit initially
Check power supply to
communicating normally fails
indoor unit.
to return signal for specified
(Is power turned on?)
Check connection of
length of time.
indoor-outdoor
communication cable.
Check connection of
communication connectors
on indoor P.C. board.
Check connection of
communication connectors
on outdoor P.C. board.
Check for defect in indoor
P.C. board.
Check for defect in outdoor
P.C. board (I/F).
Signal cannot be transmitted
Check outdoor termination
resistance setting (SW30,
from outdoor to indoor units
Bit 2).
for 30 seconds continuously.
Check connection of
indoor-outdoor
communication circuit.