Electric Wiring Work - Daikin FXHQ32MVE Installation Manual

Hide thumbs Also See for FXHQ32MVE:
Table of Contents

Advertisement

• For left drain pipe outlet, remove the rubber plug and the
insulation on the drain pipe connecting opening on the
left side of the unit and change the position to the right
side.
• Insert the rubber stopper securely, all the way to the
base, in order to prevent water leakage.
• The diameter of the drain pipe should be greater than or
equal to the diameter of the connecting pipe. (Vinyl tube;
pipe size: 20 mm; outer dimension: 26 mm)
• Keep the drain pipe short and sloping downwards at a
gradient of at least 1/100 to prevent air pockets from
forming. (Refer to Fig. 21)
• Use the drain hose (1) and the metal clamp (2).
Insert the drain hose into the drain socket, up to the gray
tape. (Refer to Fig. 22)
Tighten the metal clamp until the screw head is less than
4 mm from the hose. (Refer to Fig. 23)
(Be careful of the installation direction. Install so that the
metal clamp does not contact the intake grill.)
• Wrap the sealing pad (8) (accessory) over the clamp and
drain hose to insulate. (Refer to Fig. 23)
• No folding of drain hose inside the indoor unit.
(Refer to Fig. 24)
(If there is slack in the drain hose, it may cause damage
to the intake grill.)
(When drain hose is connected)
ood
Wrong
Do not lift
Fig. 21
Metal clamp (2) (accessory)
aping area
ig. 22
ealing pad (8)
(accessory)
Metal clamp (2)
(accessory)
< Facing rear right or right >
ig. 23
8
ilt down
Make sure there
is no slack
Make sure it is
not in the water
Drain hose (1)
(accessory)
Metal clamp (2)
(accessory)
ealing pad (8)
(accessory)
(length : mm)
< Facing rear left or left >
NOTE
NOTE
NOTE
NOTE
• To ensure no excessive pressure is applied to the included
drain hose (1), do not bend or twist when installing. (This may
cause leakage.)
• If converging multiple drain pipes, install according to the
procedure shown below.
T-joint converging drain pipes
Slope downwards at a gradient
of at least / 00
Select converging drain pipes whose gauge is suitable for the
operating capacity of the unit.
Fig. 24
(2) Confirm that smooth drainage is achieved after the pip-
ing work.
• Add 0.6 liter of water in the drain pan from the air outlet
for confirming drainage. (Refer to Fig. 25)
Portable pump
Bucket
ig. 25
CAUTION
• Drain piping connections
Do not connect the drain piping directly to sewage pipes that
smell of ammonia. The ammonia in the sewage might enter
the indoor unit through the drain pipes and corrode the heat
exchanger.
• Keep in mind that it will become the cause of getting drain
pipe blocked if water collects on drain pipe.
8.

ELECTRIC WIRING WORK

8-1
GENERAL INSTRUCTIONS
• Make certain that all electric wiring work is carried out by
qualified personnel according to the applicable legislation
and this installation manual, using a separate dedicated cir-
cuit.
Insufficient capacity of the power supply circuit or improper
electrical construction may lead to electric shocks or a fire.
• Make sure to install an earth leakage breaker.
Failure to do so may cause electric shocks and a fire.
• Do not turn on the power supply (branch switch, branch over-
current circuit breaker) until all the works are finished.
rong
ir outlet
English