• It is not necessary to designate indoor unit address when
using group control. The address is automatically set when
power is activated.
[ PRECAUTIONS ]
1. A single switch can be used to supply power to units on the
same system. However, branch switches and branch circuit
breakers must be selected carefully.
2. Do not ground the equipment on gas pipes, water pipes or
lightning rods, or crossground with telephones. Improper
grounding could result in electric shock.
9-3
Control by 2 Remote Controllers (Controlling 1
indoor unit by 2 remote controllers)
• When using 2 remote controllers, one must be set to "MAIN"
and the other to "SUB".
MAIN/SUB CHANGEOVER
(1) Insert a
screw driver into the recess between the upper
and lower part of remote controller and, working from the 2
positions, pry off the upper part. The remote controller PC
board is attached to the upper part of remote controller.
Insert the screwdriver
here and gently work
off the upper part of
remote controller
English
BS unit
Control box
IN/D
OUT/D
IN/D
F
F
F
F
F
F
2
1
2
1
2
1
Most
L N
P
P
F
F
T
T
1
2
1
2
1
2
downstream
indoor unit
P
P
1
2
pper part of
remote controller
Lower part of
remote controller
(2) Turn the MAIN/SUB changeover switch on one of the two
remote controller PC boards to "S". (Leave the switch of the
other remote controller set to "M".)
(Factory setting)
F
2
Only one remote
controller needs
to be changed if
factory settings
have remained
untouched.
Wiring Method (See ''ELECTRIC WIRING WORK'')
(3) Remove the electric parts box lid
(4) Add remote control 2 (slave) to the terminal block for
remote controller (P
(There is no polarity.) (Refer to Fig. 30 and 8-3.)
9-4
FOR REMOTE CONTROL (FORCED OFF AND
ON/OFF OPERATION)
(1) Wire specifications and how to perform wiring
• Connect input from outside to terminals T1 and T2 of the
terminal block for remote controller.
Wire specification
Gauge
Length
External terminal
(2) Actuation
• The following table explains FORCED OFF and ON/OFF
OPERATIONS in response to Input A.
FORCED OFF
Input "ON" stops operation (impossible by
remote controllers.)
Input OFF enables control by remote
controller.
(3) How to select FORCED OFF and ON/OFF OPERATION
• Turn the power on and then use the remote controller to
select operation.
9-5
CENTRALIZED CONTROL
• For centralized control, it is necessary to designate the group
No. For details, refer to the manual of each optional control-
lers for centralized control.
M
Remote
controller
PC board
M
, P
) in the electric parts box.
1
2
2 T1 T2
ORCED
O
Input A
Sheathed vinyl cord or cable (2 wire)
0.75 - 1.25 mm
2
Max. 100 m
Contact that can ensure the minimum
applicable load of 15 V DC, 1 mA.
ON/OFF OPERATION
Input OFF → ON turns ON
unit.
Input ON → OFF turns OFF
unit.