Toshiba MMD-AP0076BHP1-E Service Manual page 78

Table of Contents

Advertisement

Check code
Outdoor 7-segment display
Main
remote
Check
Sub-code
controller
code
P13
P13
01: TS
condition
P15
P15
02: TD
condition
P17
P17
P18
P18
Location
Description
System status
of
detection
I/F
Outdoor liquid
All stop
backflow
detection error
I/F
Gas
All stop
leakdetection
(TS1 condition)
I/F
Gas leak
All stop
detection
(TD condition)
I/F
Discharge
All stop
temperature
TD2 error
I/F
Discharge
All stop
temperature
TD3 error
78
Error detection
Check items (locations)
condition(s)
<During cooling operation>
Check full-close operation
When system is in cooling
of outdoor PMV (1, 2, 4).
operation, high pressure is
Check for defect in Pd or
detected in follower unit that
Ps sensor.
has been turned off.
Check gas balancing
<During heating operation>
circuit (SV2) for clogging.
When system is in heating
Check balance pipe.
operation, outdoor PMV 1 or
Check SV3B circuit for
2 continuously registers
clogging.
opening of 100p or less while
Check defect in outdoor
P.C. board (I/F).
under SH control.
Check capillary of oil
separator oil return circuit
for clogging.
Check for leakage of check
valve in discharge pipe
convergent section.
Protective shutdown due to
Check for insufficiency in
sustained suction
refrigerant quantity.
temperature at or above
Check outdoor service
judgment criterion
valves (gas side, liquid
for at least 10 minutes is
side) to confirm full
repeated four times or more.
opening.
<TS error judgment criterion>
Check PMVs (PMV1, 2) for
In cooling operation: 60 " C
clogging.
In heating operation: 40 " C
Check resistance
characteristics of TS1
sensor.
Check for defect in 4-way
valve.
Check SV4 circuit for
leakage
Protective shutdown due to
Check for insufficiency in
sustained discharge
refrigerant quantity.
temperature (TD1, TD2 or
Check PMVs (PMV 1, 2)
TD3) at or above 108 " C for at
for clogging.
Check resistance
least 10 minutes is repeated
four times or more.
characteristics of TD1, TD2
and TD3 sensors.
Check indoor filter for
clogging.
Check piping for clogging.
Check SV4 circuit (for
leakage or coil installation
error).
Discharge temperature (TD2)
Check outdoor service
exceeds 115 " C.
valves (gas side, liquid
side) to confirm full
opening.
Check outdoor PMVs
(PMV1, 2, 4) for clogging.
Check resistance
characteristics of TD2
sensor.
Check for defect in 4-way
valve.
Check SV4 circuit for
leakage.
Check SV4 circuit (for
wiring or installation error
involving SV41, SV42 and
SV43).
Discharge temperature (TD3)
Check outdoor service
exceeds 115 " C.
valves (gas side, liquid
side) to confirm full
opening.
Check outdoor PMVs
(PMV1, 2, 4) for clogging.
Check resistance
characteristics of TD3
sensor.
Check for defect in 4-way
valve.
Check SV43 circuit for
leakage.
Check SV4 circuit (for
wiring or installation error
involving SV41, SV42 and
SV43).