Toshiba MMD-AP0076BHP1-E Service Manual page 69

Table of Contents

Advertisement

Check code
Outdoor 7-segment display
Main
remote
Check
Sub-code
controller
code
F07
F07
F08
F08
F10
F11
F12
F12
01: Compressor 1
side
02: Compressor 2
F13
side
03: Compressor 3
side
F15
F15
F16
F16
F22
F22
F23
F23
Location
Description
System status
of
detection
I/F
TL sensor
All stop
error
I/F
TO sensor
All stop
error
Indoor
Indoor TA
Stop of
unit
sensor error
corresponding
unit
Indoor
Indoor TF
Stop of
unit
sensor error
corresponding
unit
I/F
TS1 sensor
All stop
error
IPDU
TH sensor
All stop
error
I/F
Outdoor
All stop
temperature
sensor wiring
error (TE1,
TL)
I/F
Outdoor
All stop
pressure
sensor wiring
error (Pd, Ps)
I/F
TD3 sensor
All stop
error
I/F
Ps sensor
All stop
error
69
Error detection
Check items (locations)
condition(s)
Sensor resistance is infinity
Check connection of TL sensor
or zero (open / short
connector.
circuit).
Check resistance
characteristics of TL sensor.
Check for defect in outdoor
P.C. board (I/F).
Sensor resistance is infinity
Check connection of TO
sensor connector.
or zero (open / short
circuit).
Check resistance
characteristics of TO sensor.
Check for defect in outdoor
P.C. board (I/F).
Sensor resistance is infinity
Check connection of TA
or zero (open / short
sensor connector and wiring.
circuit).
Check resistance
characteristics of TA sensor.
Check for defect in indoor P.C.
board.
Sensor resistance is infinity
Check connection of TF
or zero (open / short
sensor connector and wiring.
circuit).
Check resistance
characteristics of TF sensor.
Check for defect in indoor P.C.
board.
Sensor resistance is infinity
Check connection of TS1
or zero (open / short
sensor connector.
circuit).
Check resistance
characteristics of TS1 sensor.
Check for defect in outdoor
P.C. board (I/F).
Sensor resistance is infinity
Defect in IGBT built-in
temperature sensor
or zero (open / short
circuit).
→ Replace A3-IPDU P.C.
board.
During compressor
Check installation of TE1 and
TL sensors.
operation in HEAT mode,
TE1 continuously provides
Check resistance
temperature reading
characteristics of TE1 and TL
higher than indicated by TL
sensors.
by at least specified margin
Check for outdoor P.C. board
for 3 minutes or more.
(I/F) error.
Readings of high-pressure
Check connection of high-
Pd sensor and lowpressure
pressure Pd sensor connector.
Ps sensor are
Check connection of lowp-
switched.
ressure Ps sensor connector.
Output voltages of both
Check for defect in pressure
sensors Pd and Ps.
sensors are zero.
Check for error in outdoor P.C.
board (I/F).
Check for deficiency in
compressive output of
compressor.
Sensor resistance is infinity
Check connection of TD3
sensor connector.
or zero. (open / short
circuit)
Check resistance
characteristics of TD3 sensor.
Check for defect in outdoor
P.C. board (I/F).
Output voltage of Ps
Check for connection error
involving Ps sensor and Pd
sensor is zero.
sensor connectors.
Check connection of Ps sensor
connector.
Check for defect in Ps sensor.
Check for deficiency in
compressive output of
compressor.
Check for defect in 4-way
valve.
Check for defect in outdoor
P.C. board (I/F).
Check for defect in SV4 circuit.