Connecting up
6.2 Suitable cables for power supply and Ethernet
Application
Ethernet
Fiber-optic cable multimode
(for device variants with optical connectors)
Only use cables suitable for high temperatures!
If temperatures in excess of 70 °C occur on the cable or at the housing socket, or the
temperature at the branching points of the cables exceeds 80 °C, special measures need to
be taken.
If the equipment is operated in an air ambient at 45 - 60 °C, only use cables with admitted
maximum operating temperature of at least 90 °C.
38
WARNING
Specification
1. IE FC TP standard cable GP 2 x 2 (type A)
Order no.: 6XV1 840-2AH10
2. IE TP torsion cable 2 x 2 (type C)
Order no.: 6XV1 870-2F
3. IE FC TP trailing cable 2 x 2 (type C)
Order no.: 6XV1 840 3AH10
UL listing: Type PLTC or ITC (the three named types
have this approval)
FO standard cable GP
order no. 6XV1 873-2A
Minimum bending radius 65 mm.
You will find detailed information on preassembled
cable lengths in the "Catalog IK PI".
FO Robust Cable GP 2G50/125/900
Order no. 6XV1873-2R
Halogen-free, UV-resistant cable for indoors and
outdoors for ambient temperatures -40 °C ... +70 °C.
Operating Instructions, 11/2014, A5E03678337-07