SETTING ALL THE PARAMETERS
To save all the parameters it is necessary to reach the end of the guided
procedure until the last screen previously shown. If the procedure is
interrupted earlier, none of the parameters previously set will be saved.
6.5

SETTING THE MODBUS PARAMETERS

The parameters regarding the communication via RS485 interface can
be set in the MODBUS menu.
Modbus address
MODBUS ADDRESS:
202
Parameter
MODBUS ADDRESS
6.6

UPS TEST

The UPS TEST menu allows for the carrying out of a switching test of
the inverter. The inverter is switched off and the load is transferred to the
bypass supply. The inverter supply is automatically restored after a few
seconds.
UPS TEST
NO
(1x)
UPS TEST
YES
SPECIAL
UPS TEST
POSSIBLE LOSS OF SUPPLY
In case of power failure while the test is being performed, the immediate
operation of the inverter is not guaranteed.
The single digits can be modified via the
arrow keys (
/
pressing
(ENTER).
Standard
1
The value on the second line is ready to
be changed
The parameter is changed. The change
is confirmed by pressing
The system performs a test and returns
to the previous screen
) and confirmed by
Range
1 O. 247
(ENTER)