Item
Link bits (LR area)
Timers/counters
CompoBus/S master functions
DeviceNet slave functions
DM area
Read/write
Read only
Inverter interface
Encoder interface
PLC setup
Interrupts
High-speed counters High-speed counter 1 input,
see note 5
Differential phase mode (5 kHz)
Pulse plus direction input mode
(20 kHz)
Up/down input mode (20 kHz)
Increment mode (20 kHz)
Interrupt inputs (counter mode)
2 inputs
Incrementing counter (2 kHz)
Decrementing counter (2 kHz)
Encoder interface
Pulse outputs
Synchronized pulse control
Pulse catch inputs
Analog volume
Input time constant
(ON response time = OFF response time)
Clock/Calendar function
Communication function
G7/F7/L7/E7 inverter PLC
Specifications
3G3RV-P10ST8-E
256 bits: LR 0000 to LR 1515 (words LR 00 to LR 15)
256 timers/counters (TIM/CNT 000 to TIM/CNT)
1-ms timers: TMHH(--)
10-ms timers: TIMH(15)
100-ms timers: TIM
1-s/10-s timers: TIML(--)
Decrementing counters: CNT
Reversible counters: CNTR(12)
Remote I/O devices can be allocated up to 256 I/O points (128 inputs and 128 outputs) in input area IR 020 to
IR 027 and output area IR 030 to IR 037.
• The node numbers can be set to 0 to 7 (128-point mode) or 0 to 15 (256-point mode).
• The communications mode can be set to high-speed mode (max. length 100 m) or long-distance mode
(max. length 500 m).
Up to 64 words (32 input words and 32 output words) can be allocated to the DeviceNet master's I/O.
The master's I/O can be allocated to the following data areas:
IR 000 to IR 049
IR 200 to IR 227
DM 0000 to DM 2047
LR 00 to LR 15
HR 00 to HR 19
AR 00 to AR 23 (3G3RV-P10ST ' master; read-only)
TC 000 to TC 255
• Explicit message communications are supported. Any 3G3RV-P10ST data area can be accessed from the
DeviceNet master.
• The communications speed can be set to 500 kbps (total network length 100 m max.), 250 kbps (total network
length 250 m max.), or 125 kbps (total network length 500 m max.).
2,029 words (DM 0000 to DM 0999, DM 1019 to DM 2047)
DM 2000 to DM 2021: error log storage area
456 words (DM6144 to 6599)
19 words (DM 2022 to DM 2040)
14 words (DM 1986 to DM 1999)
56 words (DM 6599 to DM 6655)
Interrupt inputs
2 inputs
Response time: 50 µs
Interval timer interrupts
1 input
Set value: 0.5 to 319,968 ms
Precision: 0.1 ms
No interrupt
Count-check interrupt
(An interrupt can be generated when the count equals the set value or the count lies within a preset range.)
No interrupt
Count-up interrupt
3 input modes:
Differential-phase (up/down)
Pulse plus direction
Up/down pulse
Maximum input frequency 50 kHz
Maximum counter range 4,294,967,295 (232-1)
Two capture registers, 3 selectable registration inputs
One comparison value
Counter reset through software or Z-phase
Interrupt function
• 2 outputs:
Single-phase pulse output without acceleration/deceleration (see note 6.)
10 Hz to 10 kHz
• 2 outputs:
Variable duty ratio pulse output (see note 6.)
0.1 to 999.9 Hz, duty ratio 0 to 100%
• 1 output:
Pulse output with trapezoidal acceleration/deceleration (see note 6.)
Pulse plus direction output, up/down pulse output, 10 Hz to 10 kHz
1 point, see notes 5 and 6
Input frequency range: 10 to 500 Hz, 20 Hz to 1 kHz, or 300 Hz to 20 kHz
Output frequency range: 10 Hz to 10 kHz
2 bits
Minimum pulse input: 50 µs max.
Used in common by input interrupts and input interrupt counter mode.
None
Determines the input time constant for all inputs. (settings: 1, 2, 3, 5, 10, 20, 40, or 80 ms)
Shows the current year, month, day of the week, day of the month, hour, minute, and second.
Port 1 = Peripheral and RS-422:
Host link, peripheral bus, no-protocol, programming console
Port 2 = RS-232C port:
Host link, no-protocol, 1:1 PLC link, 1:1 NT link
3G3RV-P10ST8-DRT-E
Scheduled interrupts
One-shot interrupt
367

Hide quick links:

Advertisement

Table of Contents
loading