Operating Conditions - Buderus Logano GE434 Maintenance Instructions Manual

Table of Contents

Advertisement

12
Boiler operating conditions for countries outside the EU

12.9 Operating conditions

Always maintain the operating conditions to safeguard
the perfect boiler function. It may be necessary to install
a second annular butterfly valve with actuator motor
(Fig. 31, Item 1) (accessory) in place of the adaptor
(Fig. 31, Item 2) in the l.h. boiler block. This is the case,
– if no external components are used to reduce the
volume flow (e.g. control of the heating circuit
actuators or external butterfly valve through the
control unit), and
– if the functionality of the control unit used cannot
maintain the Buderus Ecostream conditions
(Buderus control units for modulating low
temperature operation, applicable for medium and
large boilers are equipped with this control logic).
In such cases, please contact your nearest Buderus
sales office.
Boiler
Boiler water volume
in conjunction with a Logamatic control device for modulating low-temperature operation
Logano
No requirements
GE434
in conjunction with a Logamatic control device for constant boiler water temperatures, expanded by external control
Logano
No requirements
GE434
Tab. 31 Operating conditions
1
If heating circuits (pumps, actuators) or a boiler circuit actuator (control of the operating flow temperature) cannot be regulated via the control
device, an operating temperature of 50 °C must be reached within 10 minutes of switching the burner ON by means of restricting the volume flow.
2
Boiler control thermostat setting: When the burner is ON, the minimum boiler water temperature inside the boiler must be reached and maintained
as minimum temperature within 10 minutes by suitable means, e.g. a reduction in volume flow.
We reserve the right to make any changes due to technical modifications.
Commissioning and maintenance instructions Logano GE434 Gas-fired special boiler • Issue 02/2003
66
Operating flow
flow
temperature at burner
No requirements
Operating temperatures are
safeguarded by the
Logamatic control device
Fig. 31
Adaptor
Item 1: Annular butterfly valve with actuator motor
Item 2: Adaptor
Operating conditions
Operating interruption
(complete boiler
"ON"
No requirements
1
2
60 °C
No requirements
Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
2
Min. return temperature
shutdown)
No requirements