Heating system inspection and maintenance
! Clean and assemble the pilot burner.
! Fit the clean-out cover above the gas burner.
PLEASE NOTE
When fitting the gas burner, ensure that
the spacers are located on the threaded
studs.
! Carry out the gas burner assembly and installation in
reverse order to their removal (see "Removing the
gas burner", page 36).
! Replace gaskets, if necessary.
RISK TO LIFE
through the explosion of volatile gases.
Leaks may have been created on pipes
WARNING!
and fittings by the maintenance work.
! Carry out a proper leak test.
! Only use approved leak test agents to
discover leaks.
8.5

Internal leak test

! Check the inlet side of the gas train with a test
pressure of at least 100 mbar and maximum
150 mbar for internal leaks.
After one minute, the pressure drop may be a maximum
of 10 mbar.
Should the pressure drop be greater, carry out a full leak
test with foaming leak detector spray on all gas train
sealing points. Repeat the leak test, if you discover a
leak.
Replace the gas train, if you cannot detect a leak, and
the pressure drop is again greater than 10 mbar per
minute.