Way Valve Control; Outdoor Fan Motor Control - Panasonic CS-W7DKE Service Manual

Table of Contents

Advertisement

8.5.11. Overload Protection Control
Outdoor Fan Control
• If the temperature of the indoor heat exchanger rises to 51°C, outdoor fan stops. The outdoor fan restarts when the indoor
heat exchanger temperature falls to 49°C.
Compressor high pressure protection
• If the indoor heat exchanger becomes 65°C or more, the compressor will stop and restart automatically.
(Time Delay Safety Control - 4 minutes waiting).
• This is to reduce the pressure, as to reduce the indoor heat exchanger temp. Nevertheless, is to protect the compressor
from overload of too high temperature.

8.5.12. 4-Way Valve Control

• 4-way valve always on during Heating operation. (except deicing operation)
• When the unit is switched off by remote control during Heating operation, the 4-way valve stay at Heating position for 5 minutes.
• This is to prevent the refrigerant flow process sound for being occur.

8.5.13. Outdoor Fan Motor Control

• When compressor stops (reaches room temperature), outdoor fan will operate for 30 seconds (forced operation).
• This is to release the heat and to obtain the lowest pressure as fast as possible.
8.5.14. Hot Start Control
• Hot Start Control is to prevent cool air discharge into the room when heating operation start.
• When Heating operation starts, Indoor fan will not start until the indoor heat exchanger reaches 30°C as diagram shown.
• Hot start is completed when indoor heat exchanger rises to 39°C or operation over 4 minutes.
CS-W7DKE CU-W7DKE / CS-W9DKE CU-W9DKE / CS-W12DKE CU-W12DKE
27