Fan Blank; Flash-Backed Write Cache Procedures - HP ProLiant DL360p Gen8 Maintenance And Service Manual

Hide thumbs Also See for ProLiant DL360p Gen8:
Table of Contents

Advertisement

Install the access panel
2.
Slide the server into the rack.
3.
Power up the server.
4.

Fan blank

Install fans 1 and 2 only when processor 2 is installed. When only one processor is installed, install the fan
blanks in bays 1 and 2
To remove the component:
Power down the server (on page 25).
1.
Remove all power:
2.
Disconnect each power cord from the power source.
a.
Disconnect each power cord from the server.
b.
Extend the server from the rack (on page 26).
3.
Remove the access panel
4.
Remove the fan blanks.
5.
To replace the component, reverse the removal procedure.

Flash-backed write cache procedures

Two types of procedures are provided for the FBWC option:
Removal and replacement of failed components:
Removing the cache module
o
Removing the capacitor pack
o
Recovery of cached data from a failed server
on page 42)
CAUTION: Do not detach the cable that connects the battery pack or capacitor pack to the
cache module. Detaching the cable causes all data in the cache module to be lost.
("Access
panel" on page 27).
("Fan
modules" on page 84).
("Access
panel" on page 27).
("Cache
module" on page 41)
("FBWC capacitor
pack" on page 41)
("Recovering data from the flash-backed write
Removal and replacement procedures 40
cache"

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents