Capacity Compensation Rate For Pipe Length; Capacity Compensation Rate For Pipe Length And Height Difference - Fujitsu AS*G07LECA Design & Technical Manual

Wall mounted type
Hide thumbs Also See for AS*G07LECA:
Table of Contents

Advertisement

5.

CAPACITY COMPENSATION RATE FOR PIPE LENGTH

AND HEIGHT DIFFERENCE
MODEL
: AOG07LE, AOG09LE
COOLING
Indoor unit is
upper than
outdoor unit.
Height
difference H
(m)
Indoor unit is
under than
outdoor unit
HEATING
Indoor unit is
upper than
outdoor unit.
Height
difference H
(m)
Indoor unit is
under than
outdoor unit
Indoor unit
Connection pipe
 1 Indoor unit is upper than outdoor unit.
15
Û 1
10
7.5
5
0.992
0
1.000
-5
1.000
Û 2
-7.5
-10
-15
15
Û 1
10
7.5
5
1.000
0
1.000
-5
0.995
Û 2
-7.5
-10
-15
Height difference H
Outdoor unit
- (02 - 07) -
Pipe length (m)
5
7.5
-
-
-
-
0.961
-
0.979
0.965
0.983
0.969
0.991
0.976
0.991
0.976
-
0.991
0.976
-
-
0.976
-
-
Pipe length (m)
5
7.5
-
-
-
-
0.917
-
0.961
0.917
0.961
0.917
0.961
0.917
0.956
0.912
-
0.954
0.910
-
-
0.908
-
-
Outdoor unit
Connection pipe
 2 Indoor unit is under than outdoor unit.
10
15
-
0.872
0.910
0.886
0.925
0.890
0.929
0.893
0.933
0.901
0.940
0.901
0.940
0.901
0.940
0.901
0.940
-
0.901
0.940
10
15
-
0.832
0.822
0.832
0.822
0.832
0.822
0.832
0.822
0.832
0.822
0.828
0.818
0.826
0.816
0.824
0.814
-
0.815
0.805
Indoor unit
20
20