9-2
WIRING EXAMPLE
CAUTION
Be sure to install an earth leakage breaker to the outdoor
unit.
This is to avoid electric shocks or a fire.
For the wiring of outdoor units, refer to the installation manual
attached to the outdoor units. Confirm the system type.
• Pair type:
1 remote controller controls 1 indoor unit (standard system).
(Refer to Fig. 31)
• Simultaneous operation system:
1 remote controller controls 2 indoor units
(2 indoor units operates equally). (Refer to Fig. 32)
• Group control:
1 remote controller controls up to 16 indoor units
(All indoor units operate according to the remote controller).
(Refer to Fig. 33)
• 2 remote controllers control:
2 remote controllers control 1 indoor unit. (Refer to Fig. 36)
Pair type
Earth leakage
breaker
Outdoor unit
1 2 3
Indoor unit
Remote controller
(Optional accessory)
Fig. 31
Simultaneous operation system
Earth leakage
breaker
Outdoor unit
1 2 3
NOTE 1)
1 2 3
P1 P2
Indoor unit (Master)
P1 P2
NOTE 2)
Fig. 32
13
Power supply
220 - 240V
~
50Hz
1 2 3
NOTE 1)
P1 P2
P1P2
Power supply
220 - 240V
~
50Hz
1 2 3
P1 P2
Indoor unit (slave)
Remote
controller
(Optional accessory)
NOTE
NOTE
NOTE
NOTE
1. Terminal numbers of outdoor and indoor units must be
matched.
2-1. Connect the remote controller only to the master unit.
2-2. The remote controller needs to be wired only to the mas-
ter unit; it does not need to be connected to the slave
units through transition wiring. (Do not connect transition
wiring to the slave units.)
2-3. The indoor temperature sensor is effective only for indoor
units to which the remote controller is connected.
2-4. The length of wiring between the indoor unit and the out-
door unit varies depending on the connected model, the
number of connected units, and the maximum piping
length.
For details, refer to the technical documents.
Group control
Power supply
220 - 240V
~
50Hz
Earth leakage
Earth leakage
breaker
breaker
Outdoor unit
Outdoor unit
1 2 3
NOTE)
1 2 3
1 2 3
P1 P2
Indoor unit
Indoor unit
(Master)
P1 P2
Group control remote controller
(Optional accessory)
NOTE
NOTE
NOTE
NOTE
• Terminal numbers of outdoor and indoor units must be
matched.
When implementing group control
• When using as a pair unit or as a master unit for simultane-
ous operation system, you may carry out simultaneous start/
stop (group) control up to 16 units with the remote controller.
(Refer to Fig. 34)
• In this case, all the indoor units in the group will operate in
accordance with the group control remote controller.
• Select a remote controller which matches as many of the
functions (airflow direction, etc.) in the group as possible.
Outdoor
unit 1
Indoor
Indoor
unit 2
unit 1
(Slave)
Group control remote controller
Fig. 34
Wiring Method
(1) Remove the control box lid. (Refer to ''9. HOW TO CON-
NECT WIRINGS AND WIRING EXAMPLE''.)
Power supply
Power supply
220 - 240V
220 - 240V
~
~
50Hz
50Hz
Earth leakage
breaker
Outdoor unit
1 2 3
1 2 3
NOTE)
NOTE)
1 2 3
P1 P2
P1 P2
Indoor unit
Fig. 33
Outdoor
Outdoor
unit 2
unit 16
Indoor
unit 2
Indoor
(Master)
unit 16
English