(4) Connect the remote controller wiring led from the routing
hole to the terminals (P1 and P2) of the terminal block
(X1M: 4P). (There is no polarity.)
After this is done, use the wiring fixture (11) and clamp (4)
attached to bind the wiring without applying tension to the
connecting section of the wirings.
Terminal block (X2M)
R10 or more
Transmission and earth wiring connection method
Outdoor unit
Terminal block
Terminal numbers of outdoor and
indoor units must be matched
Transmission wiring connection method
Forbidden
• Do not carry out soldering finish.
Forbidden
• Never connect the power supply
wiring.
• Do not carry out soldering finish.
Terminal block (X1M)
Remote controller
R10 or more
wiring
(no polarity)
Remote controller wiring
connection method
Printed Circuit
Board
Control box
Cut off the
knockout hole and
put the resin
bushing
(10) (accessory)
Control box lid
fixing screws
(2 pieces)
Wiring diagram Label (Rear)
English
Earth terminal
R10 or more
Transmission wiring
and Earth wiring
Indoor unit
Terminal block
Wiring penetration
hole
Rear piping
Transmission
penetration
wiring and
cover
Earth wiring
Remote controller
wiring
Control box lid
WARNING
When wiring, form the wirings orderly so that the control
box lid can be securely fastened. If the control box lid is not
in place, the wirings may float up or be sandwiched by the
box and the panel and cause electric shocks or a fire.
Remote controller wiring
Wiring fixture
(11) (accessory)
(1) Install the fixture at
the wiring entrance
side.
Power supply wiring
DETAIL
and Earth wiring
• In case the piping penetration cover is cut off and used as
wiring penetration hole, after the wiring connection is fin-
ished, mend the cover.
• Seal the clearance around the wirings with putty and insulat-
ing material (field supply).
(If insects and small animals get into the indoor unit, short cir-
cuiting may occur inside the control box.)
• If the low voltage wiring (remote controller wiring) and the
high voltage wiring (transmission wiring, earth wiring) are
brought into the indoor unit from the same place, they may be
affected by electric noise (outside noise) and cause malfunc-
tion or failure.
• Keep the distance of 50mm or more between the low voltage
wiring (remote controller wiring) and the high voltage wiring
(transmission wiring, earth wiring) at anywhere outside the
indoor unit. If both the wirings are laid down together, they
may be affected by electric noise (outside noise) and cause
malfunction or failure.
Transmission
wiring and
Earth wiring
Resin bushing
(10)(accessory)
High voltage wiring
Distance of 50mm between
Clamp (4) (accessory)
(2) Fix the wiring to the
fixture by clamps so
that no tension will be
given to the terminal
connection.
Clamp (4) (accessory)
(3) To avoid the loosing of
the power supply
wiring and Earth
wiring, band the clamp
to tightly fit the fixture
at terminal block side.
Putty or insulation
(field supply)
Refrigerant piping
Remote controller
wiring
Drain piping
Low voltage wiring
12