Hitachi RAF-25FX8 Service Manual page 128

Room air conditioner
Table of Contents

Advertisement

Available languages

Available languages

< Reference >
When operation stop with LD301 blinks 12 times, it may be caused by faulty DC fan motor.
In this case, please check CN6 and CN12 connection first. It makes Fan Motor Lock also if those
connectors are in misconnection.
DC Fan Motor has broken invites 1A Fuse burned. Please replace both DC Fan Motor and 1A Fuse
together.
It will makes "Fan Lock Stop" when something has disturb the Fan rotation by inserting materials into
propeller fan or ice has growing inside of outdoor unit by snowing.
It may make "Fan Lock Stop" by strong wind (ex. 17m/sec. or above) against the Fan rotation. In this case
unit will be restart again after a while.
In case of " Fan Lock Stop" even though the DC Fan Motor is rotating correctly, the possible cause in
Fan Motor problem or control board problem. Stop after the Fan motor runs 2 minutes, Fan Motor may
be broken.
< Caution >
Please take care for the electrical shock by high voltage of DC Fan Motor power source which is common
with compressor when you are servicing this unit.
You can not confirm the coil and wiring of Motor directly due to the built in control circuit in Fan Motor.
– 146 –

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rac-25fx8Raf-35fx8Rac-35fx8

Table of Contents