Environmental Type Tests - Siemens RUGGEDCOM RX1500 Installation Manual

Hide thumbs Also See for RUGGEDCOM RX1500:
Table of Contents

Advertisement

Chapter 6
Certification
IEEE 1613 (C37.90.x) EMI Immunity Type Tests
NOTE
The RX1500 meets Class 2 requirements for an all-fiber configuration and Class 1 requirements for
copper ports.
Test
IEEE C37.90.3
IEEE C37.90.2
IEEE C37.90.1
IEEE C37.90.1
IEEE C37.90
IEEE C37.90

Environmental Type Tests

Test
IEC 60068-2-1
IEC 60068-2-2
IEC 60068-2-30
IEC 60255-21-1
IEC 60255-21-2
44
Description
ESD
Radiated RFI
Fast Transient
Oscillatory
H.V. Impulse
Dielectric Strength
Description
Cold Temperature
Dry Heat
Humidity (Damp Heat, Cyclic)
Vibration
Shock
Enclosure Contact
Enclosure Air
Enclosure ports
Signal ports
D.C. Power ports
A.C. Power ports
Earth ground ports
Signal ports
D.C. Power ports
A.C. Power ports
Signal ports
D.C. Power ports
A.C. Power ports
Signal ports
D.C. Power ports
A.C. Power ports
Test Ad
Test Bd
Test Db
95% (non-condensing), 55 °C (131 °C), 6 cycles
RUGGEDCOM RX1500
Installation Guide
Test Levels
+/-2 kV, +/-4 kV, +/- 8 kV
+/-4 kV, +/-8 kV, +/-15 kV
35 V/m
+/- 4 kV @ 2.5 kHz
+/- 4 kV
+/- 4 kV
+/- 4 kV
2.5 kV common mode @1MHz
2.5 kV common, 1 kV
differential mode @ 1 MHz
2.5 kV common, 1 kV
differential mode @ 1 MHz
5 kV (Fail-Safe Relay Output)
5 kV
5 kV
2 kVAC
1.5kVDC
2 kVAC
Test Levels
-40 °C (-40 °F), 16 Hours
85 °C (185 °F), 16 Hours
2 g @ 10-150 Hz
30 g @ 11 mS
EMI and Environmental Type Tests

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ruggedcom rx1512

Table of Contents