Airflow Performance; Airflow - Side Duct Application - York PCE4 Series Installation Manual

Single package air conditioner/electric
Table of Contents

Advertisement

5126744-UIM-D-1015
COMPRESSORS
The compressor used in this product is specifically designed to operate
with R-410A Refrigerant and cannot be interchanged.
CAUTION
!
This system uses R-410A Refrigerant which operates at higher pres-
sures than R-22. No other refrigerant may be used in this system.
The compressor uses polyolester (POE oil), Mobile 3MA POE. This oil
is extremely hygroscopic, meaning it absorbs water readily. POE oil can
absorb 15 times as much water as other oils designed for HCFC and
CFC refrigerants. If refrigerant circuit is opened, take all necessary pre-
cautions to avoid exposure of the oil to the atmosphere.
CAUTION
!
Do not leave the system open to the atmosphere. Unit damage could
occur due to moisture being absorbed by the POE oil in the system.
This type of oil is highly susceptible to moisture absorption
SECTION V: AIRFLOW PERFORMANCE
Table 9: Airflow - Side Duct Application
Model
Motor Speed
Low (1)
Low/Medium (2)
A24
Medium (3)
Medium/High (4)
High (5)
Low (1)
Low/Medium (2)
A30
Medium (3)
Medium/High (4)
High (5)
Low (1)
Low/Medium (2)
A36
Medium (3)
Medium/High (4)
High (5)
Low (1)
Low/Medium (2)
A42
Medium (3)
Medium/High (4)
High (5)
Low (1)
Low/Medium (2)
B48
Medium (3)
Medium/High (4)
High (5)
Low (1)
Low/Medium (2)
B60
Medium (3)
Medium/High (4)
High (5)
1. Airflow tested with dry coil conditions, without air filters, at 230 volts.
2. Applications above 0.8" w.c. external static pressure are not recommended.
3. Brushless DC high efficiency standard ECM blower motor used for all indoor blower assemblies.
4. Minimal variations in airflow performance data results from operating at 208 volts. Data above may be used in those cases.
5. Heating applications tested at 0.50" w.c. esp, and cooling applications tested at 0.30" w.c.esp per standards.
14
External Static Pressure (Inches WC)
0.1
0.2
0.3
SCFM
SCFM
SCFM
887
847
802
978
941
898
1171
1114
1074
1349
1297
1265
1487
1462
1392
1076
1020
984
1102
1048
1010
1191
1140
1112
1201
1225
1187
1370
1329
1283
1225
1174
1131
1259
1209
1166
1314
1271
1229
1348
1306
1259
1506
1471
1403
1436
1382
1342
1544
1492
1455
1573
1523
1484
1681
1640
1599
1935
1887
1834
1620
1564
1517
1694
1630
1580
1798
1722
1669
1835
1758
1703
2146
2085
2025
1730
1682
1628
1858
1807
1749
2054
1998
1934
2195
2144
2098
2445
2388
2306
POE (polyolester) compressor lubricants are known to cause long term
damage to some synthetic roofing materials.
CAUTION
!
Exposure, even if immediately cleaned up, may cause embrittlement
(leading to cracking) to occur in one year or more. When performing
any service that may risk exposure of compressor oil to the roof, take
precautions to protect roofing.
Procedures which risk oil leakage include, but are not limited to, com-
pressor replacement, repairing refrigerant leaks, replacing refrigerant
components such as filter drier, pressure switch, metering device or
coil.
Units are shipped with compressor mountings which are factory-
adjusted and ready for operation.
CAUTION
!
Do not loosen compressor mounting bolts.
0.4
0.5
SCFM
SCFM
750
705
850
803
1039
993
1224
1185
1331
1318
943
903
974
934
1076
1038
1151
1118
1271
1209
1090
1046
1126
1084
1186
1144
1222
1179
1389
1345
1304
1262
1416
1376
1445
1408
1557
1517
1788
1743
1466
1418
1530
1482
1620
1572
1653
1604
1960
1872
1592
1552
1710
1667
1890
1843
2049
2003
2293
2235
0.6
0.7
SCFM
SCFM
SCFM
664
613
759
713
949
906
1146
1107
1063
1281
1241
1201
859
819
890
850
1000
958
1080
1041
1002
1176
1143
1109
993
941
1032
980
1097
1049
1133
1086
1036
1305
1262
1216
1220
1179
1131
1336
1294
1248
1367
1327
1279
1478
1436
1393
1701
1651
1591
1360
1308
1206
1430
1380
1292
1527
1480
1413
1558
1511
1442
1862
1798
1735
1517
1479
1439
1629
1589
1546
1801
1757
1710
1955
1883
1868
2178
2129
2077
Johnson Controls Unitary Products
0.8
563
667
864
779
810
919
888
928
998