Figure 1. Sample Humidification Applications Room-Sensed %Rh Feedback With Duct Hi-Limit Sensing; Figure 2. Sample Humidification Applications Control Feedback (0-100%) With Duct Hi-Limit Sensing - Nortec NHTC Series Installation Manual

Nortec humidifier installation manual
Hide thumbs Also See for NHTC Series:
Table of Contents

Advertisement

Configuration Variables
nviInputType_x = 1
nviNetSensor_x = 1
Control Variables
nviSet1_x = Room Setpoint (0-100%)
nviSet2_x = Hi-Limit Setpoint (0-100%)
nviRHDem1_x = Room %RH (0-100%)
nviRHDem2_x = Hi-Limit %RH (0-100%)
nviDisable_x = 1 Unit Disabled
= 0 Unit Enabled
Readable Variables
nvoStatus_x = 1 Humidifying
= 0 Standby
nvoService_x = 1 Service Required
= 0 No Service Required
nvoFault_x = 1 Fault
= 0 No Fault
nvoSysDemand_x = System Demand(0-100%)
nvoDisable_x = 1 Unit Disabled
= 0 Unit Enabled
Figure 1. Sample Humidification Applications
Room-Sensed %RH Feedback with Duct Hi-Limit Sensing
Configuration Variables
nviInputType_x = 0
nviNetSensor_x = 1
Control Variables
nviSet1_x = Room Setpoint (0-100%)
nviSet2_x = Hi-Limit Setpoint (0-100%)
nviRHDem1_x = Room %RH (0-100%)
nviRHDem2_x = Hi-Limit %RH
nviDisable_x = 1 Unit Disabled
= 0 Unit Enabled
Readable Variables
nvoStatus_x = 1 Humidifying
= 0 Standby
nvoService_x = 1 Service Required
= 0 No Service Required
nvoFault_x = 1 Fault
= 0 No Fault
nvoSysDemand_x = System Demand(0-100%)
nvoDisable_x = 1 Unit Disabled
= 0 Unit Enabled
Figure 2. Sample Humidification Applications
Control Feedback (0-100%) with Duct Hi-Limit Sensing
NHTC
(0-100%)
NHTC
10-10
Page 16
2008-02-18