Wall Mount General Information; Wall Mount Model Nomenclature; Shipping Damage; General - Bard C24H1-A Installation Instructions Manual

Table of Contents

Advertisement

WALL MOUNT GENERAL INFORMATION

HEAT PUMP WALL MOUNT MODEL NOMENCLATURE
C
36
MODEL
NUMBER
CAPACITY |
24 - 2 Ton
H - Heat Pump
30 - 2½ Ton
36 - 3 Ton
42 - 3½ Ton
VOLTS & PHASE
48 - 4 Ton
A - 230/208/60/1
B - 230/208/60/3
60 - 5 Ton
C - 460/60/3
VENTILATION OPTIONS
B - Blank-off Plate
V - Commercial Ventilator - Mod. Spring Return w/Exhaust
S - Economizer (Internal) - Fully Modulating with Exhaust
R - Energy Recovery Ventilator - Motorized with Exhaust
(See Spec. Sheet S3459)
Note  All 230/208V units with or without electric heat have circuit breaker. 0C is for 460V circuit breaker & 0KW. No 460V electric heat options w/circuit
breaker available. 460V -0Z and all 460V KW options are with Rotary Disconnect. See available heater options by unit model number.

SHIPPING DAMAGE

Upon receipt of equipment, the carton should be
checked for external signs of shipping damage. If
damage is found, the receiving party must contact
the last carrier immediately, preferably in writing,
requesting inspection by the carrier's agent.

GENERAL

The equipment covered in this manual is to be installed by
trained, experienced service and installation technicians.
The refrigerant system is completely assembled and
charged. All internal wiring is complete.
The unit is designed for use with or without duct work.
Flanges are provided for attaching the supply and return
ducts.
These instructions explain the recommended method to
install the air cooled self-contained unit and the electrical
wiring connections to the unit.
Manual 2100-586D
Page
4 of 25
H
1
A
KW
REVISIONS
0C - 0KW
0Z - 0KW
04 - 4KW
05 - 5KW
06 - 6KW
F8 - 8KW
S8 - 8KW
09 - 9KW
10 -10KW
15 -15KW
20 -20KW
WARNING
Falling or tipping the unit could cause injury or death!
Use two (2) people or a machine to move the unit.
05
V
P
COLOR OPTIONS
X - Beige
1 - White
4 - Buckeye Gray
5 - Desert Brown
8 - Dark Bronze
S - Stainless Steel
FILTER OPTIONS
X - 1-Inch Fiberglass (MERV 2)
M - 2-Inch Pleated (MERV 11)
P - 2-Inch Pleated (MERV 8)
These instructions and any instructions packaged with
any separate equipment required to make up the entire
air conditioning system should be carefully read before
beginning the installation. Note particularly "Starting
Procedure" and any tags and/or labels attached to the
equipment.
While these instructions are intended as a general
recommended guide, they do not supersede any national
and/or local codes in any way. Authorities having
jurisdiction should be consulted before the installation
is made. See Page 3 for information on codes and
standards.
Size of unit for a proposed installation should be based
on heat loss/gain calculation made according to methods
of Air Conditioning Contractors of America (ACCA).
The air duct should be installed in accordance with the
Standards of the National Fire Protection Association
for the Installation of Air Conditioning and Ventilating
Systems of Other Than Residence Type, NFPA No.
90A, and Residence Type Warm Air Heating and Air
Conditioning Systems, NFPA No. 90B. Where local
regulations are at a variance with instructions, installer
should adhere to local codes.
X
X
X
X
CONTROL MODULES
(See Spec. Sheet S3459)
COIL OPTIONS
X - Standard Hydrophilic Fin
Indoor Coil & Uncoated
Aluminum Outdoor Coil
1 - Phenolic Coated Indoor Coil
2 - Phenolic Coated Outdoor Coil
3 - Phenolic Coated ID & OD Coil
SUPPLY AIR OUTLET
X - Front (Standard)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents