Sub-Cool Heat Ex. Gasinlet Thermistor Error - Fujitsu AOYG45LAT8 User Manual

Hybrid flex inverter system
Hide thumbs Also See for AOYG45LAT8:
Table of Contents

Advertisement

Trouble shooting 23
OUTDOOR UNIT Error Method:

Sub-cool Heat EX. GasInlet Thermistor Error

Detective Actuators:
Sub-cooling heat exchanger gas inlet
temperature thermistor
Forecast of Cause :
1. Connector connection defective, open
2. Thermistor failure3. Main PCB failure
Check Point 1 : Check the connector connection and cable open
Connector connection state check
Cable open check
OK
Check Point 2 : Check the thermistor
Thermistor characteristics check (Disconnect the thermistor from the PCB and check.)
* For the thermistor characteristics, refer to the "Service Parts Information 5".
OK
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Main PCB (CN65:1-2) voltage value = 5V
Remove the thermistor from Main PCB, check the voltage.
Sub-cooling heat exchanger gas inlet thermistor (CN65:1-2)
If the voltage does not appear, replace Main PCB
and execute the check operation again.
Indicate or Display:
Outdoor Unit : E. 82. 1
Indoor Unit
Error Code
Detective details:
Sub-cooling heat exchanger gas inlet temperature thermistor short or
open detected
1 2 3 4
1 2 3 4
CN65
,
: Operation LED 8 times Flash, Timer LED 2 Times Flash,
Economy LED Continuous Flash.
: 82
DC
02-39

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents