1-11. TEST OPERATION CONTROL
< Pre-test run check items >
Before the test run, refer to the figure and check the following items.
1. Is check run performed? Test run doesn't operate if check run is not performed.
After checking that the above items are all in order, refer to Test run method "to test run the unit.
If there are problems, adjust immediately and recheck.
< Test run method >
Be sure to configure test run settings only when the outdoor unit has stopped operating.
Depending on the communication status between the indoor and outdoor units, it may take several minutes for
the system to start operating after settings for the test run are complete.
After the test run settings are complete, all the outdoor units and the connected indoor units will start operating.
Room temperature control will not activate during test run (continuous operation).
Test run set with the outdoor unit doesn't stop automatically. Be sure to stop the operation according to the
operation method.
All indoor units will operate when test run is performed from the outdoor unit. At this time, the remote controller of
the indoor unit is unavailable.
Operation mode cannot be changed during the test run. To change the operation mode, please stop the test run
first, and then perform the test run again. At this time, the compressor cannot be restarted for three minutes after
it stops in order to protect the indoor unit. Please restarte it after three minutes.
With Wired Remote Controller
Under the condition where the air conditioner stops, press the MODE button and the FAN button
simultaneously for 2 seconds or more, and the test operation control mode will appear.
During test running, "
Set the test operation mode, and the compressor will continue to run regardless of whatever
the room temperature sensor detects.
With Wireless Remote Controller
Under the condition where the air conditioner runs, press the TEST RUN button, and
the test operation control mode will appear.
During test running, the Operation LED and Timer LED of the air conditioner body blinks simultaneously.
Set the test operation mode, and the compressor will continue to run regardless of whether the room
temperature sensor detects.
With Outdoor Unit
All the indoor units connected to the outdoor unit can be test-operated by push button as next page.
" will display on the remote controller display.