1-6. OUTDOOR FAN CONTROL
1. Fan speed table
Table 5 shows the fan speed of the outdoor unit.
( Table 5 : Outdoor fan speed table)
AOYG45LAT8
Fan step
0
1
2
3
4
5
6
7
8
9
10
11
2. Limit of fan speed range
Fig.15 shows the limit of fan speed range changes by outdoor temperature.
( Fig.15 : Limit of fan speed range )
< Cooling and Dry mode >
Outdoor
temperature
30°C
20°C
10°C
3. Initial fan speed control
Initial fan speed is decided by outdoor temperature.
( Fig.16 : Initial fan speed range )
< Cooling and Dry mode >
Outdoor
temperature
10°C
If the fan motor is running over than 400rpm, it start up process is stopped in all conditions. [ Prevent the big wind operation ]
*
When the fan motor is stopped, it can not restart for 10 seconds.
*
Even if during EEV initialization, outdoor unit fan starts.
*
[rpm]
Fan speed
0
250
290
340
390
460
580
690
800
890
910
950
890rpm
580 ~ 890rpm
250 ~ 890rpm
0 ~ 890rpm
690rpm
390rpm
< Heating mode >
Outdoor
temperature
5°C
< Heating mode >
Fixed at 690rpm
01-17
460 ~ 910rpm
460 ~ 950rpm