• Two spreader bars must span over the unit to prevent
damage to the cabinet by the lift cables. Spreader bars
must be of sufficient length so that cables do not come in
contact with the unit during transport. Remove wood
struts mounted beneath unit base frame before setting
unit on roof curb. These struts are intended to protect
unit base frame from fork lift damage. Removal is
accomplished by extracting the sheet metal retainers and
pulling the struts through the base of the unit. Refer to
rigging label on the unit.
Important: If using bottom discharge with roof curb, ductwork
should be attached to the curb prior to installing the unit. Ductwork
dimensions are shown in Roof Curb Installation Instructions.
Refer to the Roof Curb Installation Instructions for proper curb
installation. Curbing must be installed in compliance with the Na-
tional Roofing Contractors Association Manual.
Lower unit carefully onto roof mounting curb. While rigging unit,
center of gravity will cause condenser end to be lower than supply
air end.
To assist in determining rigging requirements, unit weights are
shown as follows:
A
Y
CONDENSER
COIL
COMPRESSOR
B
X
CORNER & CENTER OF GRAVITY LOCATIONS
C
RETURN
EVAPORATOR COIL
CG
SUPPLY
D
Shipping
A*
X
Y
Weight
Model
(in)
(in)
(lbs)
DCC036*
35
27
DCC048*
35
27
DCC060*
35
27
DCC072*
35
27
DCH036*
34
28
DCH048*
34
28
DCH060*
34
28
DCH072*
34
28
* Weights shown are belt drive with no accessories.
T
O PREVENT SEVERE DAMAGE TO THE BOTTOM OF THE UNIT
FORK LIFT UNIT AFTER WOOD STRUTS HAVE BEEN REMOVED
Bring condenser end of unit into alignment with the curb. With
condenser end of the unit resting on curb member and using curb
as a fulcrum, lower opposite end of the unit until entire unit is
seated on the curb. When a rectangular cantilever curb is used,
care should be taken to center the unit. Check for proper align-
ment and orientation of supply and return openings with duct.
R
R
IGGING
EMOVAL
T
O PREVENT DAMAGE TO THE UNIT
AND SPREADER BARS TO REST ON THE ROOF OF THE UNIT
Remove spreader bars, lifting cables and other rigging equipment.

ELECTRICAL WIRING

HIGH VOLTAGE!
D
ISCONNECT ALL POWER BEFORE SERVICING OR
. M
INSTALLING THIS UNIT
ULTIPLE POWER SOURCES MAY
. F
BE PRESENT
AILURE TO DO SO MAY CAUSE PROPERTY
,
DAMAGE
PERSONAL INJURY OR DEATH
HIGH VOLTAGE!
T
O AVOID PERSONAL INJURY OR DEATH DUE TO
,
ELECTRICAL SHOCK
DO NOT TAMPER WITH FACTORY
. T
WIRING
HE INTERNAL POWER AND CONTROL WIRING
OF THESE UNITS ARE FACTORY
BEEN THOROUGHLY TESTED PRIOR TO SHIPMENT
C
ONTACT YOUR LOCAL REPRESENTATIVE IF
.
ASSISTANCE IS REQUIRED
6
Corner Weights ( lbs )
Operating
Weight
A
B
(lbs)
525
500
115
150
560
535
125
160
595
570
133
167
650
625
147
185
605
580
130
180
610
585
135
185
605
580
133
182
660
635
142
200
CAUTION
CAUTION
,
DO NOT ALLOW CRANE HOOKS
WARNING
.
WARNING
-
INSTALLED AND HAVE
.
C
D
105
130
110
140
118
152
127
166
110
155
115
155
113
157
122
171
,
DO NOT
.
.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Dch series

Table of Contents