VOLTAGE
MODELS
(NAMEPLATE)
208/230-60-1
208/230-60-3
3 TON
460-60-3
575-60-3
208/230-60-1
208/230-60-3
4 TON
460-60-3
575-60-3
208/230-60-1
208/230-60-3
5 TON
460-60-3
575-60-3
208/230-60-3
6 TON
460-60-3
575-60-3

APPENDIX B ELECTRICAL DATA

ELECTRICAL DATA
VOLTAGE
COMPRESSOR
LIMITATION
MIN.
MAX.
QTY
RLA
187
253
1
16.67
187
253
1
10.45
414
506
1
5.77
518
633
1
3.8
187
253
1
19.87
187
253
1
13.14
414
506
1
6.09
518
633
1
4.4
187
253
1
26.41
187
253
1
15.96
414
506
1
7.76
518
633
1
5.71
187
253
1
19
414
506
1
9.70
518
633
1
7.4
OUTDOOR
FAN MOTOR
LRA
QTY
HP
RLA
79
1
1/4
1.40
73.0
1
1/4
1.40
38.0
1
1/4
0.80
37.0
1
1/4
0.60
109
1
1/4
1.40
83.1
1
1/4
1.40
41.0
1
1/4
0.80
33.0
1
1/4
0.60
134
1
1/4
1.40
110.0
1
1/4
1.40
52.0
1
1/4
0.80
38.9
1
1/4
0.60
123
1
1/3
1.92
62.0
1
1/3
1.20
50.0
1
1/3
0.90
22
INDOOR
INDOOR
FAN MOTOR
MOTOR
APPLICATION
HP
DD STD STATIC
1/3
DD STD STATIC
1/3
BD STD STATIC
1.0
BD STD STATIC
1.0
BD STD STATIC
1.5
DD STD STATIC
1/2
DD STD STATIC
1/2
BD STD STATIC
1.0
BD STD STATIC
1.0
BD STD STATIC
1.5
DD STD STATIC
1.0
DD STD STATIC
1.0
BD STD STATIC
1.0
BD STD STATIC
1.0
BD STD STATIC
1.5
BD STD STATIC
1.5
BD STD STATIC
1.5
BD STD STATIC
1.5
FLA
2.5
2.5
3.8
1.9
2.3
2.9
2.9
3.8
1.9
2.3
7.6
7.6
3.8
1.9
2.3
5.0
2.5
2.3

Hide quick links: