Mitsubishi Electric PCFY-P40VGM-E Technical & Service Manual page 21

Split-type, heat pump air conditioners
Hide thumbs Also See for PCFY-P40VGM-E:
Table of Contents

Advertisement

Switch
SWA
(High)
Set the
1~3
ceiling
(Standard)
height
(Low)
SWC
Option
2
Option
(Standard)
SW11
1st digit
address
setting
SW12
SW12
2nd digit
address
setting
10
SW14
Connection
No. setting
220V
SW5
Voltage
2
selection
Operation by switch
Ceiling height can be changed depends on
SW A setting.
3
2
1
When the optional high performance filter ele-
ments (filter casement) is attached to the unit,
be sure to set switch to the option side in
order to prevent the airflow reducing.
SW11
Address setting should be done when M-NET
0
0
remote controller is being used.
1
SW14
This is the switch to be used when the indoor
0
unit is operated with R2 series outdoor unit
as a set.
If the unit is used at the 230V or 240V area,
240V
set the switch to 240V side.
If the unit is used at the 220V, set the switch
to 220V side.
21
Remarks
Address board
<At delivery>
3
2
1
Address board
<At delivery>
Option
Address board
Address can be set while the
unit is stopped.
<At delivery>
SW12
SW11
0
0
Address board
<At delivery>
SW14
0
Address board
<At delivery>
220V
240V