7-2. FUNCTION OF DIP SWITCH
PCFY-P40VGM-E PCFY-P63VGM-E PCFY-P100VGM-E PCFY-P125VGM-E
Switch Pole
Function
Room temperature Thermistor
1
position
2
Filter clogging detection
3
Filter cleaning sign
4
Air intake
SW1
5
Remote indication switching
Mode
6
Humidifier control
Selection
7
Air flow set in case of
8
heat thermostat OFF
9
Auto reset function
10
Power resource ON/OFF
Capacity
SW2
PCFY-
Capacity
P40VGM-E
1~6
code
setting
PCFY-
P125VGM-E
1
Heat pump/Cool only
2
Louver
3
Vane
4
Vane swing function
SW3
5
Vane horizontal angle
Function
6
Vane cooling limit angle setting
Selection
Indoor linear expansion
7
valve opening
8
Heater 4degrees up
9
Target Superheat setting
10
Target Subcool setting
SW4
Unit
1~4
Selection
ON
Built-in remote controller
Provided
2500hr
Effective
Thermostat ON signal indication Fan output indication
Always operated while the heating mode w1 Operated depends on the condition
Fix to LOW
Depends on setting remote controller
Effective
Effective
SW2
Capacity
ON
ON
PCFY-
OFF
OFF
P63VGM-E
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
Cooling only
Available
Available
Available
Second setting
w4
Horizontal angle
Effective
Not effective
w5
9degrees
15degrees
ON
OFF
1 2 3 4 5
Operation by switch
OFF
Indoor unit
Not provided
100hr
Not effective
w3
Fix to EXTRA lOW
w3
Depends on SW1-7
Not effective
Not effective
SW2
Capacity
SW2
ON
PCFY-
OFF
P100VGM-E
1 2 3 4 5 6
1 2 3 4 5 6
Heat pump
Not available
Not available
Not available
First setting
Down B,C
Not effective
Effective
6degrees
10degrees
20
Remarks
Address board
<At delivery>
ON
OFF
1 2 3 4 5 6 7 8 9 10
NOTE:
w1 At Heating mode, fan
operating.
w2 At Heater mode, operating
w2
heat thermostat ON.
w3 SW1-7=OFF, SW1-8=ON
w3
Setting air flow.
SW1-7=ON, SW1-8=ON
Indoor fan stop.
Indoor controller board
Set while the unit is off.
<At delivery>
Set for each capacity.
Indoor controller board
Set while the unit is off.
<At delivery>
ON
OFF
1 2 3 4 5 6 7 8 9 10
NOTE:
w4 At cooling mode, each
angle can be used only 1
hour.
w5 SW3-9 setting
P40 = ON
P63,P100,P125 = OFF
Indoor controller board
Set while the unit is off.
<At delivery>
ON
OFF
1 2 3 4 5