VENTING INSTALLATION

Read all instructions completely and
thoroughly before attempting installation.
Failure to do so could result in serious
injury, property damage or loss of life.
Operation of improperly installed and
maintained venting system could result in
serious injury, property damage or loss of
life.
Failure to follow these instructions will void
the warranty.

INSTALLATION PRECAUTIONS

Consult local building codes before beginning the installa-
tion. The installer must make sure to select the proper vent
system for installation. Before installing vent kit, the installer
must read this insert manual and vent kit instructions.
Only a qualifi ed installer/service person should install vent-
ing system. The installer must follow these safety rules:
Wear gloves and safety glasses for protection.
Use extreme caution when using ladders or when
on rooftops.
Be aware of electrical wiring locations in walls and
ceiling.
The following actions will void the warranty on your venting
system:
Installation of any damaged venting component.
Unauthorized modifi cation of the venting system.
Installation of any component part not manufactured
or approved by Vermont Castings Group.
Installation other than permitted by these instruc-
tions.
This insert must be vented to the outside.
The venting system must NEVER be
attached to a chimney serving a separate
solid fuel burning appliance. Each gas
appliance must use a separate vent system.
Do not use common vent systems.
20304852

VENTING REQUIREMENTS

Make sure the exhaust pipe on heater
connects to exhaust portion of cap. At-
tach fl ex liners. Figure 9
Do not crimp or rupture liner when bend-
ing it into chimney offsets.
The exhaust vent must reline the entire length of chim-
ney and terminate above chimney top.
Vent must meet all vent manufacturer's requirements
when installed.
Make sure you have the following before installing unit:
3" and 3" UL 1777 Listed gas liner for air inlet and
exhaust.
Vertical Terminations kits:
HEDV32T812, HEDV32T1212
Inlet
Figure 9 -
Venting Unit
ICFDV40 Fireplace Insert
Exhaust
Maximum Height 40'
(12.9 m)
Minimum Height 10'
(3 m)
FP2947