Expanded operating temperature
< 1% of annual operating hours
Expanded Operating Temperature Restrictions
148
–5°C to 45°C at 5% to 90% RH with 29°C dew
point.
NOTE: Outside the standard operating
temperature (10°C to 35°C), the system can
operate down to –5°C or up to 45°C for a
maximum of 1% of its annual operating hours.
For temperatures between 40°C and 45°C, de-
rate maximum allowable temperature by 1°C per
125 m above 950 m (1°F per 228 ft).
•
Do not perform a cold startup below 5°C.
•
The operating temperature specified is for a
maximum altitude of 3050 m (10,000 ft).
•
160 W (10 core) processor is not supported.
•
Tape Backup Unit (TBU) is not supported.
•
Redundant power supplies are required.
•
Non Dell qualified peripheral cards and/or
peripheral cards greater than 25 W are not
supported.
•
PCIe SSD and GPU is not supported.
•
Maximum 120 W processor supported on 3.5
inch hard drive chassis.
•
Maximum 145 W processor supported on 2.5
inch hard drive chassis.
•
Only SSDs are allowed in the hard drive slots at
the back of the 3.5 inch hard drive chassis.