25.11. Forced operation during restart
The compressor will not stop operating for 3 minutes after cooling mode operation starts, even if the indoor unit thermostat turns
off.
(However, the compressor will stop operating during this time if the indoor unit air intake temperature drops to 16°C and below
during cooling mode operation.)
25.12. Louvre control (models with louvre)
1. When main power is turned on
When the power is turned on, indoor unit louvre position detection is carried out twice and then the indoor unit louvre stops.
2. During initial operation
When the OFF/ON button is pressed to start the operation, the louvre moves through one full cycle, and then swings
automatically (if AUTO has been set using the remote control) or moves to the setting angle (if MANUAL has been set using
the remote control).
3. When operation stops
When the OFF/ON button is pressed to stop the operation, the louvre moves through one full cycle, and then stops in the down
position, regardless of the remote control setting.
4. When thermostat is off
When operation is stopped by the indoor thermostat, the louvre moves through one full cycle, and then stops in the horizontal
position, regardless of the remote control setting.
25.13. Outdoor unit fan excess heat dissipation control
1. When the operation is stopped while the compressor is in operation, the outdoor fan will run at SUPER HI fan speed for
approximately 60 seconds and then stops.

25.14. Discharge temperature control

1. Operation
When the discharge temperature sensor detects a temperature of 100°C or higher during cooling mode operation, the liquid
bypass valve will be turned on.
2. Cancelling
When the discharge temperature sensor detects a temperature of 70°C or lower, the liquid bypass valve will be turned off.