25.10. Indoor unit fan control
1. Fixing at LO, MED or HI
When LO, MED or HI is set, the relay switches and operation is carried out at that setting.
2. Automatic fan speed
When set to AUTO, the indoor unit fan operation changes as shown in the table below.
Mode / Fan Speed
Cooling
Heating
Fan
HI
+3 or higher
-3 or lower
MED irrespective of temperature
68
(Indoor temperature) - (Setting temperature) (Units: K)
MED
+1.5 ~ 3
-1.6 ~ - 3
LO
Less than +1.5
More than -1.5