Adding Refrigerant; Condensate Drainage Connection And Safe Drainage - REMKO ML 263 DC Assembly And Operating Instructions Manual

Inverter wall-mounted room air conditioner with split design
Table of Contents

Advertisement

REMKO ML...DC

6.5 Adding refrigerant

The units contain a basic quantity of refrigerant. In
addition, an additional amount of refrigerant must
be added for refrigerant piping lengths exceeding 5
metres per circuit. Refer to the following chart:
Up to and
incl. 5m
ML 263 DC
ML 353 DC
0 g/m
ML 523 DC
CAUTION!
Wear protective clothing when handling refrig-
erant.
DANGER!
Only refrigerant in a liquid state may be used to
fill the cooling cycle!
NOTICE!
Check the overheating to determine the refrig-
erant fill quantity.
NOTICE!
The escape of refrigerant contributes to cli-
matic change. In the event of escape, refrig-
erant with a low greenhouse potential has a
lesser impact on global warming than those
with a high greenhouse potential. This device
contains refrigerant with a greenhouse poten-
tial of 1975. That means the escape of 1 kg of
this refrigerant has an effect on global warming
that is 1975 times greater than 1 kg CO
based on 100 years. Do not conduct any work
on the refrigerant circuit or dismantle the
device - always enlist the help of qualified
experts.
32
7
From 5m to
max. length
30 g/m
Fig. 38: Condensate drainage, seepage of conden-
sate and strip foundation (cross-section)
1:
2:
3:
4:
5:
6:
7:
8:
9:
2
,
10: Frost line
11: Drainage pipe
12: Soil
Condensate drainage
connection and safe
drainage
100
4
5
6
9
10
12
11
Outdoor unit
Leg
Condensate collection tray
Floor bracket
Reinforced strip foundation
HxWxD = 300x200x800mm
Gravel layer for seepage
Condensate drainage heating
Drainage channel
Conduit for refrigerant piping and electrical
connecting line (temperature-resistant up to at
least 60°C)
1
2
3
5
7
8
10
12